Indoor Air Content Sensor Settings - Honeywell Design and Application Technical Reference Manual

Design and application guide for economizer controls
Table of Contents

Advertisement

Section 8- W6215, W7215 And W7460 Economizer Modules

Indoor Air Content Sensor Settings

24VAC
Hot
24VAC
Com
+
2-10V
OUT
Free
Cool
Alarm
Unit
Control
Exhaust
Fan
Indoor
Fan
The DCV input can be any sensor with a 2 to
10 Vdc output such as the Honeywell C7242,
C7232 or C7632 carbon dioxide (CO
The sensor is supplied with preset
configurations that can be used if they meet
63-8594-02 Honeywell Economizers
ECONOMIZER
MODULE WITH
DCV SENSOR INPUT
24VAC
TR1
TR Hot
Com
B
C
+
A
D
So
+
Sr
5
1
2
Mininum
Position
3
4
SENSOR OUTPUT
T
T1
Open
P
P1
DCV SENSOR
Free Cooling
Maximum
INPUT ON
Position
TEMINALS
Q
Q1
Close
AQ
AQ AND AQ1
6V
+
AQ1
2V
10V
ISI
SD1
SD
Set Pt
AC
AC1
ISI
6V
0A1
0A
2V
100%
OSI
Set Pt
OSI
6V
2V
10V
DCV
Set Pt
)sensor.
2
74
C7242 INDOOR
AIR CONTENT
CO2 SENSOR
ROOM CONCENTRATION CARBON
IN VOLTS DC
DIOXIDE IN PARTS PER MILLION
0
500
650
1
800
2
950
3
1100
4
1250
5
6
1400
7
1550
8
1700
9
1850
10
2000
the application requirements. The output chart
illustrated on the right side of this page is the
Analog 1 configuration of startpoint and
throttling range for a linear output.
M23925A