Variable name
_EIP_TargetPLCErr [255]
Meaning
Target PLC Error Information
Function
This variable shows the error status (logical OR of fatal and non-fatal errors) of the target node Controllers that
are connected with the built-in EtherNet/IP ports as the originator.
The array elements are valid only when the corresponding Normal Target Node Information is TRUE.
The immediately preceding value is retained if this variable is FALSE.
Array[x] is TRUE: A fatal or non-fatal error occurred in the target Controller with a target node ID of x.
Array[x] is FALSE: Other than the above.
Data type
ARRAY [0..255] OF BOOL
R/W access
R
Usage in user program
Possible.
Variable name
_EIP_TargetNodeErr
Meaning
Target Node Error Information
Function
This variable indicates that the connection for the Registered Target Node Information was not established or that
an error occurred in the target Controller.
The array elements are valid only when the Registered Target Node Information is TRUE.
Array[x] is TRUE: A connection was not normally established with the target node for a target node ID of x (the
Registered Target Node Information is TRUE and the Normal Target Node Information is FALSE), or a connection
was established with the target node but an error occurred in the target Controller.
Array[x] is FALSE: The target node is not registered for a target node ID of x (the Registered Target Node Informa-
tion is FALSE), or a connection was normally established with the target node (the Registered Target Node Infor-
mation is TRUE and the Normal Target Node Information is TRUE). An error occurred in the target Controller (the
Target PLC Error Information is TRUE).
Data type
ARRAY [0..255] OF BOOL
R/W access
R
Usage in user program
Possible.
Variable name
_EIP_NTPResult
Meaning
NTP Last Operation Time
Function
Gives the last time that NTP processing ended normally.
The time that was obtained from the NTP server is stored when the time is obtained normally.
The time is not stored if it is not obtained from the NTP server normally.
Note Do not use this variable in the user program. There may be a delay in updating it. Use this variable only to
Data type
Structure: _sNTP_RESULT
Members: DATE_AND_TIME
R/W access
R
Usage in user program
Not possible.
NJ-series CPU Unit Software User's Manual (W501)
Retained
Related instruc-
tions
Retained
Related instruc-
tions
access status through communications from an external device.
Retained
Not retained.
Related instruc-
You can read the contents of this variable with the GetNTPStatus instruc-
tions
tion.
Global/local
Range of values
Not retained.
Network Publish
---
Global/local
Range of values
Not retained.
Network Publish
---
Members
Global/local
Range of values
Network Publish
Appendices
Global
TRUE or FALSE
Published.
Global
TRUE or FALSE
Published.
.ExecTime
Global
Depends on data type.
Published.
A-79