Additional Information
Hierarchical Relationship of System-defined Variables Related to EtherNet/IP Errors
The system-defined variables that are related to EtherNet/IP errors have the following hierarchi-
cal relationship. For example, if the value of any of the _EIP_PortErr, _EIP_CipErr, or
_EIP_TcpAppErr variables in the second level is TRUE, then the _EIP_ErrSta variable in the first
level also changes to TRUE. Therefore, you can check the values of system-defined variables in
a higher level to see if an error has occurred for a variable in a lower level.
Variable
_EIP_ErrSta Built-in Ether-
A-44
Level 1
Name
Variable
_EIP_PortErr
Net/IP Error
_EIP_CipErr
_EIP_TcpAppErr
Level 2
Name
Variable
Communica-
_EIP_MacAdr
tions Port Error
Err
_EIP_LanHwErr
_EIP_EtnCfgErr
_EIP_IPAdrCfg
Err
_EIP_IPAdrDupErr
_EIP_BootpErr
_EIP_IPRTblErr
CIP Communi-
_EIP_Identity
cations Error
Err
_EIP_TDLink
CfgErr
_EIP_TDLink
OpnErr
_EIP_TDLink
Err
_ EIP_TagAdr
Err
_EIP_MultiSw
ONErr
TCP Applica-
_EIP_TcpApp
tion Communi-
CfgErr
cations Error
_EIP_NTPSrv
Err
_EIP_DNSSrv
Err
NJ-series CPU Unit Software User's Manual (W501)
Level 3
Name
MAC Address Error
Communications Con-
troller Error
Basic Ethernet Set-
tings Error
TCP/IP Basic Setting
Error
IP Address Duplica-
tion Error
BOOTP Server Error
TCP/IP Advanced
Setting Error
Identity Error
Tag Data Link Setting
Error
Tag Data Link Con-
nection Failed
Tag Data Link Com-
munications Error
Tag Name Resolution
Error
Multiple Switches ON
Error
TCP/IP Setting Error
NTP Server Connec-
tion Error
DNS Server Connec-
tion Error

Hide quick links: