Contents Of Memory Used For Cj-Series Units; A-6-1 Cio Area - Omron NJ-series User Manual

Machine automation controller cpu unit software
Hide thumbs Also See for NJ-series:
Table of Contents

Advertisement

A-6
Contents of Memory Used for CJ-
series Units
You can specify addresses in the memory used for CJ-series Units for AT specifications for variables.
Details on each area are provided below.
A-6-1
CIO Area
I/O Bits
 Description
The bits in this area are allocated to input and output terminals on CJ-series Basic I/O Units. The
number of words (16 bits each) that is required for each CJ-series Basic I/O Unit are allocated in
order based on the position where the Units are connected (from left to right starting from the Unit
that is closest to the CPU Unit). Data in this area is cleared when power is cycled or when the oper-
ating mode is changed between PROGRAM and RUN mode.
 Addresses
Addresses
Range
Additional Information
You can access this area on NJ-series CPU Units through device variables allocated to I/O ports.
We therefore recommend that you do not use AT specifications to access this area. You should
use AT specifications for the CIO Area only when you specify addresses for some of the Special
Units.
CPU Bus Unit Area
 Description
The bits in this area are allocated to control and status information for CJ-series CPU Bus Units.
Each Unit is allocated 25 words based on its unit number. Data in this area is cleared when power is
cycled or when the operating mode is changed between PROGRAM and RUN mode.
 Addresses
Addresses
Range
The words that are allocated are listed in the following table.
Word addresses
CIO 1500 to CIO 1524 0
CIO 1525 to CIO 1549 1
to
CIO 1875 to CIO 1899 F
NJ-series CPU Unit Software User's Manual (W501)
Word addresses
Bit addresses
CIO 0 to CIO 159
0.00 to 159.15
Word addresses
CIO 1500 to CIO 1899
Unit Number
to
Bit addresses
CIO 1500.00 to CIO 1899.15
Appendices
Words per Unit
25 words
A-85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents