Types Of Backup Functions - Omron NJ-series User Manual

Machine automation controller cpu unit software
Hide thumbs Also See for NJ-series:
Table of Contents

Advertisement

9-1-4

Types of Backup Functions

There are backup functions for the NJ-series Controllers that save data to SD Memory Cards and oth-
ers that save data to a computer. Also, there are three methods used to execute the backup functions:
the CPU Unit front-panel DIP switches, system-defined variables, and the Sysmac Studio.
Functions That Save Data to SD Memory Cards
The SD Memory Card backup functions are used to back up, restore, and compare data on SD Memory
Cards. Related functions include disabling backups to SD Memory Cards and automatic transfers from
SD Memory Cards.
Function name
SD Memory
Backing
Card back-
up data
ups
Restor-
ing data
Verifying
data
Disabling backups to SD
Memory Cards
Automatic transfers from
SD Memory Cards
NJ-series CPU Unit Software User's Manual (W501)
CPU Unit
Description
front-panel
DIP switch
The Controller data is
saved in a backup file
on the SD Memory
Card.
The data in a backup
file on the SD Memory
Card is transferred to
the Controller.
The Controller data and
the data in a backup file
on the SD Memory
Card are compared.
You can disable back-
ing up data to SD Mem-
ory Cards.
When the power supply
is turned ON, the data
in a backup file on the
SD Memory Card is
automatically trans-
ferred to the Controller.
After the data transfer,
the operating mode of
the CPU Unit will
change to the mode
that is specified in
Startup Mode setting.
9 Backup Functions
Operating method
System-
Sysmac
defined
Studio
variables
Reference
9-2-1 Backup
(Controller to
SD Memory
Card)
9-2-2 Restore
(SD Memory
Card to Control-
ler)
9-2-3 Verify
(between Con-
troller and SD
Memory Card)
9-3 Disabling
Backups to SD
Memory Cards
9-4 Automatic
Transfers from
SD Memory
Cards
9
9-7

Hide quick links:

Advertisement

Table of Contents
loading