4 Controller Setup
 Basic I/O Units
The following settings are made in the Unit Information of the Basic I/O Units.
Setting
Access point
group
Unit Informa-
Basic Input
tion
Unit Input
Response
Note Set the
Time
informa-
tion for
each
slot.
4-12
Description
Sets the input response time (ON
response time = OFF response
time) of the Basic Input Unit. You
can set no filter or you can set the
value in increments from 0 to 32 ms.
You can increase the value to
reduce chattering and the effects of
external noise. If you decrease the
value, shorter input pulses are
received (but the pulses must be
longer than the task period).
Set
Update tim-
Default
values
ing
No filter
8 ms
When power
0.5 ms,
is turned ON
1 ms,
or the CPU
2 ms,
Unit is reset
4 ms,
8 ms,
16 ms,
or
32 ms
NJ-series CPU Unit Software User's Manual (W501)
Changes in
RUN mode
Not allowed.