Variable name
Meaning
_EIP_IPRTblErr
TCP/IP
Advanced
Setting Error
_EIP_IdentityErr
Identity Error
_EIP_TDLinkCfgErr
Tag Data Link
Setting Error
_EIP_TDLinkOpnErr
Tag Data Link
Connection
Failed
_EIP_TDLinkErr
Tag Data Link
Communications
Error
_EIP_TagAdrErr
Tag Name
Resolution Error
_EIP_MultiSwONErr
Multiple Switches
ON Error
_EIP_TcpAppCfgErr
TCP/IP Setting
Error
_EIP_NTPSrvErr
NTP Server Con-
nection Error
_EIP_DNSSrvErr
DNS Server Con-
nection Error
NJ-series CPU Unit Software User's Manual (W501)
Function
TRUE: There is an error in one of the follow-
ing settings. Or, a read operation failed.
• IP router table settings
• Hosts settings
FALSE: Normal
TRUE: The identity information (which you
cannot overwrite) is not correct. Or, a read
operation failed.
FALSE: Normal
TRUE: The tag data link settings are incor-
rect. Or, a read operation failed.
FALSE: Normal
TRUE: Establishing a tag data link connection
failed due to one of the following causes.
• The information registered for a target node
in the tag data link parameters is different
from the actual node information.
• There was no response from the remote
node.
FALSE: Other than the above.
TRUE: A timeout occurred in a tag data link
connection.
FALSE: Other than the above.
TRUE: Tag resolution failed (i.e., the address
could not be identified from the tag name).
The following causes are possible.
• The size of the network-published variable
does not agree with the tag setting.
• The I/O direction that is set in the tag data
link settings does not agree with the I/O
direction of the variable in the CPU Unit.
• There is no network-published variable in
the CPU Unit that corresponds to the tag
setting.
FALSE: Other than the above.
TRUE: More than one data link start/stop
switch changed to TRUE at the same time.
FALSE: Other than the above.
TRUE: At least one of the set values for a
TCP/IP application (FTP, NTP, SNMP) is
incorrect. Or, a read operation failed.
FALSE: Normal
TRUE: The NTP client failed to connect to the
server (timeout).
FALSE: NTP is not set or the connection was
successful.
TRUE: The DNS client failed to connect to the
server (timeout).
FALSE: DNS is not enabled. Or, DNS is
enabled and the connection was successful.
Appendices
Range of
Data type
values
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
Reference
page A-75
page A-76
page A-76
page A-76
page A-76
page A-76
page A-77
page A-77
page A-77
page A-77