Event name
Insufficient System Service Time Error
Meaning
The specified system service execution time could not be obtained.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
_<Task_name>_Exceeded
_<Task_name>_ExceedCount
_<Task_name>_LastExecTime
_<Task_name>_MaxExecTime
Cause and
Assumed cause
correction
There was not sufficient time to exe-
cute the tasks and tag data link ser-
vice.
The system service execution interval
is too short or the system service exe-
cution time ratio is too long in the Sys-
tem Service Monitoring Settings.
Attached
None
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 12-7.
NJ-series CPU Unit Software User's Manual (W501)
Source details
Major fault
Recovery
Stops.
Operation
Data type
BOOL
UDINT
TIME
TIME
Correction
Check the available time for task exe-
cution and the tag data link settings.
Increase the task periods or the
packet intervals (RPI) in the tag data
link settings to obtain enough time for
execution of the tasks and tag data
link service.
Check the effect on the processes
executed by the system services with
this operation and increase the sys-
tem service execution interval or
reduce the system service execution
time ratio.
12 Troubleshooting
Event code
60040000 hex
None
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Stops.*
Name
Task Period Exceeded Flag
Task Period Exceeded Count
Last Task Execution Time
Maximum Task Execution Time
Prevention
Set the System Service Monitoring
Settings according to the corrections
that are given on the left.
Continuously
System
12
12-25