Figure 9-42: Emergency Test - California Instruments MX30-1 User Manual

Mx series ac and dc power source series i / series ii
Table of Contents

Advertisement

User Manual - Rev AJ
Prior to the test, a range change may take place if the power source is set at the low voltage
range. Note: See Section 9.6.1.7.2 under HIGH VOLTAGE.
The ← key (backspace) will terminate the test at any time.
: A ra
ng
e change will result in
Note
acce
ptable
, th
e power source must
UNDER VOLTAGE
This test will change the output voltage for the selected phase in
1. 28V system:
0V for 7sec.
20V for 93sec.
2. 270V system:
0V for 7sec.
240V for 93sec.
The ← key (backspace) will terminate the test at any time.
9.6.1.8.4 Emergency Test
From
the M
IL7
04 DC MENU scro
keys (Figure 9-42). Press the ENTER key to start the EMERGEN
VOLTAGE
This test will change the output voltag
1. 28V syste
m:
18V for 1 minute.
29V for 1 minute.
28V for 1 minute.
2. 270V yst
s
em:
250V for 1 minute.
280V for 1 minute.
2
70V f
or 1
The ←
key (backspace) will terminate the test at any time.
MX Series
m
omentary loss of power
be
ll to
the EMERGENCY DC
Figure 9-42: Emergency T
e for the s
minute.
to
left in high range at all t
entr
est
elected phase in
California Instruments
the EUT. If this is not
im
es.
the following sequence:
y using the up and dow
CY TEST.
the following sequence:
n cursor
235