3.10.2 Clock/Lock Initialization Settings
The mo
de of operati
PROGR
AM2 screen. Since most clock and lock systems are permanently used in this
configur
ation, the clock mode can be set to EXT (External) at pow
SETUP3 screen.
Available initial settings and their relationship to the Clock and Lock mode of operation are
shown in the table below.
INITIAL SETUP 3
Field
C
LK/LOC
3.10.3 Clo
ck/Lock and External Sync Mode
Note that an MX-LKM auxiliary unit is factory configured to operate in Clock and Lock mode
whe
n EXT clock mode is selected in the PROGRAM2 screen. This means that a MX-LKS
not be used in normal external sync
can
operated in external sync mode.
Fur
thermore, since the MX-LKM master unit is factory set for Master mode of operation, it in turn
not be used as an Auxiliary source in a clock and lock configuration.
can
3.10.4
Remote Programming of Clock and Lock systems
Since clock and lock systems have multiple autonomous controllers that are synchronized in
freq
uency, remote programming of these systems req
with all MX controllers. This often precludes the use of RS232C as generally not enough serial
ports are available. The use of GPIB instead also offers the advantage of using the Group
Exe
cute Trigger (GET) capability to effect output changes on all phases (MX's) simultaneously
whi
ch is otherwise difficult to do.
To
set up a GPIB remote controlled clock and lock systems, the GPIB addresses for the
indi
vidual MX's must be set to different address values in the UTILITY1, GPIB/RS232 SETUP
scre
en.
Note: This mode of operation is not supported by the MXGUI Windows software
supplied with each MX unit.
MX Series
on o
f the MX-LKS auxiliary unit is determined by the Clock mode set in the
Parameter
STAND
MASTER
AUX

Table 3-14: Clock and Lock Initialization settings

mode. However, the MX-LKM master unit can be
er on by using the INITIAL
Description
Normal stand alone mode of operation. For
stand
ard MX power source with no clock and
lock mode of operation.
For master (-LKM) power source in clock and
lock mode of operation.
For auxiliary (-LKS) power source in clock and
lock mode of operation. Powers up with cloc
mo
de set to external.
uires that the application program deals
California Instruments
k
67