9.5.4.4 INTERHARMONICS
A single inter harmonic frequency may be generated using the INTERHARMONICS screen. This
sc en allows insertion o
re
lev l of the harmonics ran
e
harmonics screen, press the menu screen until t
9- 0. Select INTERHARM
3
IN ERHARMONICS SC
T
The inter harmonics screen will appear as shown in Figure 9-31. This screen has the following
parameters:
1. REFERENCE
2. REF. COUPL
3. REF. VOLT
4. VOLTAGE
MX Series
f any inter harmonic from 1Hz to 2400Hz in 1Hz steps. The amplitude
ge is from 0 to 20% of the programmed voltage. To select the inter
ONICS using the up or down key.

Figure 9-30: MENU 2 SCREEN

REEN

Figure 9-31: INTERHARMONICS SCREEN

This field will enable the Inter harmonics generator if ON is selected and
will disable the inter harmonics generation if OFF is selected.
If turned on, the REF. VOLT will follow the programmed voltage value.
This field must be programmed to a value if REF. COUPL is off. This
value has a range from 0 to 230 volts. This value is set to a value
equal to the phase A voltage if the REF. COUPL is turned on.
This field programs the Inter harmonic level in percentage of the
REF.VOLT. This value has a range from 0 to 20%