9.6.1.7.2 TRANSIENT TEST
From the MIL704 main menu (Figure 9-33) scroll
down cursor key
ap ear as shown in Fig
p
Th MIL704 Transient screen has the follo
e
1
HIGH VOLTAGE
2
LOW VOLTAGE
3
HIGH FREQUENCY
4
LOW
The above tests can be selected by scrolling to the highlighted selection using the up and down
key and the ENTER key to start the selected test.
HIGH VOLTAGE
This test will change the output voltage for the selected phase in the following sequence:
180V for 10 msec.
Linearly reduced to118V in 78msec.
Stay at 118V for 87msec before returning to 115V.
Prior to the test, a range change may take place if the power source is set for the low voltage
range.
The ← key (backspace) will terminate the test at any time.
Note: A range change will result in momentary loss of power to the EUT. If this is not
acceptable, the power source must be left in high range at
LOW VOLTAGE
This test will change the output voltage for the selected phase only in the following sequence:
80V for 10 msec.
Linearly increase to108V in 70msec.
Stay at 108V for 95msec before returning
Th ← key (backspace) will terminate the test at any time.
e
HIGH F
REQUENCY
Th test will change th
is
425Hz for 1 sec.
420Hz for 4 sec.
MX Series
s. Press the ENTER key to select the TRANSIENT screens. The screen will
ure 9-35.

Figure 9-35: Transient Menu

FREQUENCY
e output frequency in the following sequence:
to the TRANSIENT AC entry using the up and
wing tests:
all times.
to 115V.