The output power cables must be large enough to prevent a total voltage drop exceeding 1%
the rated output voltage between the power source and the load. Table 3-2 shows the size o
the cables that may be used. Note that wires must be sized to accommodate the maximum
current that is available. This may be a function of the voltage range and phase mode on some
MX models. If the MX has more than one output voltage range, size the wires for the lowest
available voltage range as the currents will be highest in that range.
Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate
the volta e drop
g
2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP
Load Current
65 AMPS
130 AMPS
260 AMPS
400 AMPS
Note:
Use
high temper
and/or local code regulations for proper rating and size of wire cabling prior to
installation.
MX Series
e the form of a panel-mounted socket (1 or 3 phase) of sufficient current
Not supplied with MX)
from the following formula:

Table 3-2: Suggested Output Wiring Sizes *

Wire Gauge (US)
6 AWG
4 AWG
1/0 AWG
2/0 AWG
atu
re rate
d wire. Al
Circular Mils
Metric (mm2)
(kcmils)
26.24
41.74
105.6
133.1
ways consult the National Electrical Code
California Instruments
of
f
13.3
21.1
53.5
67.4
43