GE B30 Communications Manual page 98

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MEMORY MAP
Products
Address Register name
Current Differential 87L In-Zone Transformer (Read/Write Grouped Setting)
L30, L90
601E
"
601F
Open Pole Detect (Read/Write Grouped Setting)
N60
6040
"
6041
2
"
6043
"
6045
"
6047
"
6049
"
604A
"
604B
"
604C
"
604D
"
604E
"
604F
"
6050
"
6051
Phase Comparison Negative Sequence Voltage (Read/Write Grouped Setting)
L60
6070
"
6071
"
6072
"
6073
"
6074
"
6076
"
6077
Phase Comparison Negative Sequence Current Rate of Change (ROC) (Read/Write Grouped Setting)
L60
6080
"
6081
"
6082
"
6083
"
6084
"
6085
"
6087
"
6089
"
608A
Phase Comparison Rate of Change of Positive-Sequence Current Settings (Read/Write Grouped Setting)
L60
6092
"
6093
"
6094
"
6095
"
6096
"
6097
2-78
87L Inrush Inhibit Mode
87L Inrush Inhibit Level
Open Pole Detect Function
Open Pole Detect Block
Open Pole Detect A Aux Co
Open Pole Detect B Aux Co
Open Pole Detect C Aux Co
Open Pole Detect Current Source
Open Pole Detect Current Pickup
Open Pole Detect Voltage Source
Open Pole Detect Voltage Input
Open Pole Detect Pickup Delay
Open Pole Detect Reset Delay
Open Pole Detect Target
Open Pole Detect Events
Open Pole Detect Broken Co
Negative Sequence Voltage FD Function
Negative Sequence Voltage FD Impedance 0 to 100
Negative Sequence Voltage FDL Pickup
Negative Sequence Voltage FDH Pickup
Negative Sequence Voltage FD Block
Negative Sequence Voltage FD Target
Negative Sequence Voltage FD Events
Negative Sequence di/dt FD Function
Negative Sequence di/dt FDL Pickup
Negative Sequence di/dt FDL Seal-In
Negative Sequence di/dt FDH Pickup
Negative Sequence di/dt FDH Seal-In
Negative Sequence di/dt FDH Supv
Negative Sequence di/dt FD Block
Negative Sequence di/dt FD Target
Negative Sequence di/dt FD Events
Positive-sequence Current Rate of Change
(di/dt FD) Function
Positive-sequence Current Rate of Change
(di/dt FDL) Low Pickup
Positive-sequence Current Rate of Change
(di/dt FDL) Low Seal-in
Positive-sequence Current Rate of Change
(di/dt FDH) High Pickup
Positive-sequence Current Rate of Change
(di/dt FDH) High Seal-in
Positive-sequence Current Rate of Change
(di/dt FDH) Supervision
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
0 to 3
---
1
1 to 40
%fo
0.1
0 to 1
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 5
---
1
0.05 to 20
pu
0.01
0 to 5
---
1
0 to 1
---
1
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
%
0.1
0.005 to 3
pu
0.001 F001
0.005 to 3
pu
0.001 F001
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.01 to 5
pu
0.01
0 to 10
s
0.001 F001
0.01 to 5
pu
0.01
0 to 10
s
0.001 F001
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.01 to 5
pu
0.01
0 to 10
s
0.001 F001
0.01 to 5
pu
0.01
0 to 10
s
0.001 F001
0 to 4294967295
---
1
UR FAMILY – COMMUNICATIONS GUIDE
Format
Default
F561
0 (Disabled)
F001
200
F102
0 (Disabled)
F300
0
F300
0
F300
0
F300
0
F167
0 (SRC 1)
F001
20
F167
0 (SRC 1)
F102
0 (Disabled)
60
100
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F001
100
10
50
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
10
600
F001
50
200
F300
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
10
600
F001
50
200
F300
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents