MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Data object
CDC
name
LocSetAcsOff
SPS
LocSetAcsOn
SPS
LosLife
MV
LosLifeRte
MV
LosPkt1
SPS
LossLd
ACT
Lower
SPS
MAC
VSG
3
MajorErr
SPS
ManMod
SPS
MaxAsymOp1
SPS
MaxCompHz
MV
MaxCompLevel MV
MaxIntrA
MV
MaxLoadDev
MV
MaxMotLoad
MV
MaxVal1
ASG
MinorErr
SPS
MinVal1
ASG
MMSConnects
MV
MnlCls
SPS
MnlOpn
SPS
Month1
SPS
MotLoad
MV
MotStatus
ENS
MotUnb
MV
NegTotVArh
MV
NegTotWh
MV
NeutOpn
SPS
3-212
Semantics
Indicates operations of FlexLogic operand ACCESS LOC SETG OFF
Indicates operations of FlexLogic operand ACCESS LOC SETG ON
XFMR LIFE LOST actual values
DAILY RATE LOL actual values
The lost packet threshold has been exceeded.
The 87L DIFF CH 1 LOSTPKT operand, which becomes On when the differential
element has detected the lost packet threshold has been exceeded on channel 1.
The high impedance fault phase A, B, C loss of load element has operated
PID Lower operand. The PID 1 LOWER operand value.
Expected value of Destination MAC address field in messages subscribed to by
RxGOOSE#
Any of the major self-test errors generated (major error).
The ANY MAJOR ERROR operand.
Capacitor control in manual mode.
The CAP 1 IN MAN operand.
Asymmetry on the channel exceeded pre-set value.
The 87L DIFF CH 1 MAX ASYM operand, which becomes On when the Asymmetry
on channel 1 exceeded preset value.
The frequency of the learned maximum broken rotor bar spectral component.
MAXIMUM COMPONENT FREQ. in Hz.
Indicates the learned maximum level of the broken rotor bar spectral component
since the last data clear.
MAXIMUM COMPONENT LEVEL in dB.
Indicates Breaker Arcing Current per phase.
BKR 1 AMP MAX phase A/B/C.
Indicates the motor load standard deviation at the time when data for the
maximum broken rotor bar was acquired.
LOAD DEV. AT BRB MAX in x FLA.
Indicates the average motor load at the time when data for the maximum broken
rotor bar was acquired.
MOTOR LOAD AT BRB MAX in x FLA.
Maximum value in deadband calculations
Any of the minor self-test errors generated (minor error).
The ANY MINOR ERROR operand.
Minimum value in deadband calculations
Number of MMS client connections active
Manual close initiated.
The BREAKER 1 MNL CLS operand.
Manual open initiated.
The BREAKER 1 MNL OPEN operand.
Current month, where 1 = January.
The MONTH operand.
The average motor load at the time of the broken rotor bar data acquisition stage.
MOTOR LOAD AT BRB CALC. in x FLA
Indicated the status of the motor (in Actual Values) where 0 = Offline, 1= Starting,
2 = Running and 3 = Overload.
Thermal Model MOTOR STATUS.
% thermal model motor unbalance.
THERMAL MODEL MOTOR UNBALANCE in percentage (%).
SRC 1 Total VAr-hour in negative direction
SRC 1 Total Watt-hour in negative direction
Indicates source has lost voltage signal.
The SRC1 VT NEU WIRE OPEN operand.
CHAPTER 3: IEC 61850 COMMUNICATION
Used in logical nodes...
SecGSAL
SecGSAL
LosLifSPTR
LosLifSPTR
LinDfPDIF
HiZPHIZ
PIDRegFPID
LGOS
LPHD
CapCtlGAPC
LinDfPDIF
BknRotSVBR
BknRotSVBR
CBArcΘSCBR
BknRotSVBR
BknRotSVBR
TDCInGGIO1,
TDCOutGGIO1
LPHD
TDCInGGIO1,
TDCOutGGIO1
LPHD
Bkr0XCBR
Bkr0XCBR
TmDayGAPC
BknRotSVBR
MotThmPTTR
MotThmPTTR
EnrMtrMMTR
EnrMtrMMTR
VtffGAPC
UR FAMILY – COMMUNICATIONS GUIDE