GE B30 Communications Manual page 452

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Data object
CDC
name
PhDir1
SPS
PhsAInd
SPS
PhsBInd
SPS
PhsCInd
SPS
PlOpn
ACT
3
PosTotVArh
MV
PosTotWh
MV
ProcBusFail
SPS
ProcBusTrbl
SPS
ProjectedDif
MV
ProjectedV1
CMV
PtpFail
SPS
Raise
SPS
RawAnsp
MV
RawAPh
WYE
RecBlk
SPS
RecEna
SPS
RefWinding
INS
RelDpo
SPS
RemCmdAcsOff SPS
RemCmdAcsOn SPS
RemMod
SPS
RemSetAcsOff
SPS
RemSetAcsOn
SPS
RemUnA
SPS
ReSigma
SPC
Restart
SPS
RgDstIP
VSG
RgRxMode
ENG
RgSrcIP
VSG
3-214
Semantics
Indicates Phase Comparison of differential is satisfied per phase, where the last
digit of instance number 1, 2, or 3 refers to phase A, B, and C respectively.
The BUS 1 DIR A/B/C operand.
The STATOR DIFF1 DIR A/B/C operand.
An LED.
The LED PHASE A operand.
An LED.
The LED PHASE B operand.
An LED.
The LED PHASE C operand.
Open pole detector is operated.
The OPEN POLE OP operand.
SRC 1 Total VAr-hour in positive direction
SRC 1 Total Watt-hour in positive direction
Process bus system status.
The PROCESS BUS FAILURE operand.
Process bus trouble.
The PROCESS BUS TROUBLE operand.
Phase angle difference between V1 and projected V2 (V2').
SYNCHROCHECK 1 DELTA PHASE', in degrees which is the phase angle difference
between V1 and projected V2.
Projected V2 Voltage phasor.
SYNCHROCHECK 1 V2' voltage phasor, in primary volts.
Bad PTP Signal.
The PTP FAILURE operand.
PID 1 RAISE operand value
Raw neutral split phase current. Raw INsp in per unit.
Raw Id in per unit for Phase A, B, and C
Manually block autoreclose.
The BREAKER 1 BLK RCLS operand.
Manually enable autoreclose.
The BREAKER 1 ENA RCLS operand.
Reference winding. Number of windings used as the reference winding for ratio
compensation.
This data object indicates that not all criteria are fulfilled, and the switching/
operation action is not released to proceed. Complement of Rel.
The SYNC 1 CLS DPO operand, which becomes Off when all synchrocheck criteria
are fulfilled.
Indicates operations of FlexLogic operand ACCESS REM CMND OFF
Indicates operations of FlexLogic operand ACCESS REM CMND ON
Capacitor control in remote mode.
The CAP 1 IN REMOTE operand.
Indicates operations of FlexLogic operand ACCESS REM SETG OFF
Indicates operations of FlexLogic operand ACCESS REM SETG ON
Indicates remote open pole condition is detected in phase A, B, or C.
The OPEN POLE REM OP phase A/B/C operand.
Command for the Hi-Z Sigma Value Reset
Indicates the motor has restarted.
The MOTOR RESTART operand.
Expected value of Destination IP address field in messages subscribed to by
RxGOOSE#. The multicast IP address of subscribed R-GOOSE message.
R-RxGOOSE1 Reception Mode setting: 0 = Unicast, 1 = SSM; 2=ASM
Expected value of Source IP address field in messages subscribed to by
RxGOOSE#. The source IP address of subscribed R-GOOSE message.
CHAPTER 3: IEC 61850 COMMUNICATION
Used in logical nodes...
B_DifPDIF, BusDifPDIF,
SttDifPDIF
LEDsIHMI
LEDsIHMI
LEDsIHMI
OpnPlΘSCBR
EnrMtrMMTR
EnrMtrMMTR
LPHD
LPHD
SynChkRSYN
SynChkRSYN
LPHD
PIDRegFPID
NeAUnPTOC
PhAUnPTOC
Bkr0XCBR
Bkr0XCBR
PctDifPDIF
SynChkRSYN
SecGSAL
SecGSAL
CapCtlGAPC
SecGSAL
SecGSAL
OpnPlΘSCBR
HiZPHIZ
MotThmPTTR
LGOS
LGOS
LGOS
UR FAMILY – COMMUNICATIONS GUIDE