GE B30 Communications Manual page 348

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-128: Undercurrent data objects
LNName: UnCurPTUC1
data obj. data attribute
StrAlm
general
dirGeneral
Str
general
dirGeneral
OpAlm
general
Op
3
general
BlkRefγ
setSrcRef
setSrcCB
3.5.2.79 Underfrequency (UnHz)
This element is instantiated in the following products: D30, D60, F35, F60, G30, G60, L30, L90, M60, N60, T35, T60.
Table 3-129: Underfrequency data objects
LNName: UnHzPTUF#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
BlkRef1
setSrcRef
setSrcCB
3.5.2.80 Underpower (UnPwr)
This element is instantiated in the following products: M60.
Table 3-130: Underpower data objects
LNName: UnPwrPDUP#
data obj. data attribute
StrAlm
general
dirGeneral
Str
general
dirGeneral
OpAlm
general
Op
3-110
LDevice inst: Prot
UR element: Undercurrent element
Type
FC UR Name
ACD
BOOLEAN
ST
U/CURR ALARM PKP
ENUMERATED
ST
ACD
BOOLEAN
ST
U/CURR TRIP PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
U/CURR ALARM OP
ACT
BOOLEAN
ST
U/CURR TRIP OP
ORG
ObjectReference SP
UNDERCURRENT BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Underfrequency element #
Type
FC UR Name
ACD
BOOLEAN
ST
UNDERFREQ # PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
UNDERFREQ # OP
SPS
BOOLEAN
ST
UNDERFREQ # DPO
ORG
ObjectReference SP
UNDERFREQ # BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Under Power element
Type
FC UR Name
ACD
BOOLEAN
ST
UNDERPWR # ALARM PKP
ENUMERATED
ST
ACD
BOOLEAN
ST
UNDERPWR # TRIP PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
UNDERPWR # ALARM OP
ACT
CHAPTER 3: IEC 61850 COMMUNICATION
Description
U/CURR ALARM PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
U/CURR TRIP PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
U/CURR ALARM OP operand
U/CURR TRIP OP operand
UNDERCURRENT BLOCK setting in setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
UNDERFREQ # PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
UNDERFREQ # OP operand
UNDERFREQ # DPO operand
UNDERFREQ # BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
UNDERPWR # ALARM PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
UNDERPWR # TRIP PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
UNDERPWR # ALARM OP operand
UNDERPWR # TRIP OP operand
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all