GE B30 Communications Manual page 394

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: ConInGGIO1
data obj. data attribute
Ind2Θ
stVal
Ind2Θ
stVal
Ind1Θ
stVal
3.5.4.6 Contact output interface (ConOut)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
3
Table 3-177: Contact output data objects
LNName: ConOutGGIO1
data obj. data attribute
Ind1Θ
stVal
Ind2Θ
stVal
Ind3Θ
stVal
Ind4Θ
stVal
InRef1Θ
setSrcRef
setSrcCB
InRef2Θ
setSrcRef
setSrcCB
InRef3Θ
setSrcRef
setSrcCB
3.5.4.7 Disconnect switch (Disc)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-178: Disconnect switch DiscCSWI data objects
LNName: DiscCSWI#
data obj. data attribute
Mod
stVal
ctlModel
Health
stVal
3-156
LDevice inst: System
UR element: Contact Inputs
Type
FC UR Name
SPS
BOOLEAN
ST
Cont Ip φ Off
SPS
BOOLEAN
ST
Cont Ip φ Off
SPS
BOOLEAN
ST
Cont Ip φ On
LDevice inst: System
UR element: Contact Outputs
Type
FC UR Name
SPS
BOOLEAN
ST
Cont Op φ IOn
SPS
BOOLEAN
ST
Cont Op φ VOn
SPS
BOOLEAN
ST
Cont Op φ VOff
SPS
BOOLEAN
ST
Cont Op φ On
ORG
ObjectReference SP
CONTACT OUTPUT φ OPERATE
setting
ObjectReference SP
ORG
ObjectReference SP
CONTACT OUTPUT φ SEAL-IN
setting
ObjectReference SP
ORG
ObjectReference SP
OUTPUT φ RESET setting
ObjectReference SP
LDevice inst: System
UR element: Disconnect Control element #
Type
FC UR Name
INC
ENUMERATED
ST
CtlModels
CF
INS
ENUMERATED
ST
LPHD1.PhyHealth.stVal
CHAPTER 3: IEC 61850 COMMUNICATION
Description
Con Ip Θ Off (φ) operand value
Instantiated only if the order code has
more than 99 contact inputs
Instantiated only if the order code has
more than 99 contact inputs
Description
only instantiated where the order code
indicates that contact output Θ is
equipped with a current detector
only instantiated where the order code
indicates that contact output Θ is
equipped with a voltage detector
only instantiated where the order code
indicates that contact output Θ is
equipped with a voltage detector
Con Op Θ On (φ) operand value
CONTACT OUTPUT φ OPERATE setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
only instantiated where the order code
indicates that contact output Θ is not a
latching output.
reference to the data attribute to input
source GoCB of input if via GOOSE
only instantiated where the order code
indicates that contact output Θ is a
latching output.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
This logical node's mode
1 (on)
0 (status only)
This logical node's health
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/W/C
R/Ctrl
R
R
R
R

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents