GE B30 Communications Manual page 392

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-174: Breaker control data objects
LNName: BkrΘXCBR#
data obj. data attribute
Mod
stVal
ctlModel
Health
stVal
Loc
stVal
OpCnt
stVal
3
units
units.SIUnit
units.multiplier
BadSt1
stVal
ClsSt1
stVal
OpnSt1
stVal
IntermSt1
stVal
Pos
stVal
ctlModel
BlkOpn
stVal
ctlModel
BlkCls
stVal
ctlModel
CBOpCap
stVal
InRef1
setSrcRef
setSrcCB
cdcNs
cdcName
3-154
LDevice inst: System
UR element: Breaker Control element #
Type
FC UR Name
INC
ENUMERATED
ST
CtlModels
CF
INS
ENUMERATED
ST
LPHD1.PhyHealth.stVal
SPS
BOOLEAN
ST
Bkr0XCBR#.Loc.stVal
INS
INT32
ST
Unit
CF
ENUMERATED
ENUMERATED
SPS
BOOLEAN
ST
BREAKER # ψ BAD ST
SPS
BOOLEAN
ST
BREAKER # ψ CLSD
SPS
BOOLEAN
ST
BREAKER # ψ OPEN
SPS
BOOLEAN
ST
BREAKER # ψ INTERM
DPC
CODED ENUM
ST
CtlModels
CF
SPC
BOOLEAN
ST
Bkr0XCBR#.BlkOpn.stVal
CtlModels
CF
SPC
BOOLEAN
ST
Bkr0XCBR#.BlkCls.stVal
CtlModels
CF
INS
ENUMERATED
ST
ORG
GEORG
ObjectReference SP
BREAKER # φA/3P CLSD if Θ="1",
BREAKER # φB CLSD if Θ="2", or
BREAKER # φC CLSD if Θ="3"
VISIBLE
SP
STRING255
ObjectReference SP
VISIBLE
SP
If reference is external to this
STRING255
IED, mapped to the source's
GOOSE control block, else empty
string
VISIBLE
EX
Name of the GE Multilin
STRING255
namespace at the time of this
firmware release
VISIBLE
EX
GEORG
STRING255
CHAPTER 3: IEC 61850 COMMUNICATION
Description
This logical node's mode
1 (on)
0 (status only)
This logical node's health
Value of operand selected by setting
XCBR# ST.LOC OPERAND
Phase ψ breaker operations counter.
1
0
BREAKER # ψ BAD ST operand
BREAKER # ψ CLSD operand
BREAKER # ψ OPEN operand
BREAKER # ψ INTERM operand
Breaker φψ position status
0
Breaker open commands blocked from
all sources including protection
0
Breaker close commands blocked from
all sources including protection
0
Mandatory data object which in this case
is fixed at 3
3
BREAKER # φA/3P CLSD setting" if Θ="1",
"BREAKER # φB CLSD setting" if Θ="2", or
"BREAKER # φC CLSD setting" if Θ="3
reference to the data attribute to input
source GoCB of input if via GOOSE
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R/Ctrl
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/C
R/C
R
R

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents