GE B30 Communications Manual page 399

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: Disc0XSWI#
data obj. data attribute
Type
InRef5
ORG
GEORG
setSrcRef
ObjectReference SP
VISIBLE
STRING255
setSrcCB
ObjectReference SP
VISIBLE
STRING255
cdcNs
VISIBLE
STRING255
cdcName
VISIBLE
STRING255
Table 3-181: Disconnect switch DiscΘXSWI data objects
LNName: DiscΘXSWI#
data obj. data attribute
Type
Mod
INC
stVal
ENUMERATED
ctlModel
CtlModels
Health
INS
stVal
ENUMERATED
Loc
SPS
stVal
BOOLEAN
OpCnt
INS
stVal
INT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
SwTyp
ENS
INS
stVal
BOOLEAN
SwOpCap
INS
stVal
ENUMERATED
BadSt1
SPS
stVal
BOOLEAN
ClsSt1
SPS
stVal
BOOLEAN
OpnSt1
SPS
stVal
BOOLEAN
IntermSt1
SPS
stVal
BOOLEAN
Pos
DPC
stVal
CODED ENUM
ctlModel
CtlModels
BlkOpn
SPC
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: System
UR element: Disconnect Control element #
FC UR Name
XSWI# ST.LOC OPERAND
SP
Reference to the ultimate source
of value selected by setting
XSWI# ST.LOC OPERAND
SP
If reference is external to this
IED, mapped to the source's
GOOSE control block, else empty
string
EX
Name of the GE Multilin
namespace at the time of this
firmware release
EX
GEORG
LDevice inst: System
UR element: Disconnect Control element #
FC UR Name
ST
CF
ST
LPHD1.PhyHealth.stVal
ST
Disc0XSWI#.Loc.stVal
ST
CF
ST
ST
ST
SWITCH # φψ BAD STATUS
ST
SWITCH # φψ CLOSED
ST
SWITCH # φψ OPEN
ST
SWITCH # φψ INTERM
ST
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
XSWI# ST.LOC OPERAND (local control)
setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
This logical node's mode
1 (on)
0 (status only)
This logical node's health
Value of operand selected by XSWI#
ST.LOC OPERAND
Phase ψ disconnect switch operation
counter.
1
0
Disconnect switch type, fixed at 2
(Disconnector)
2
Mandatory data object which in this case
is fixed at 4
4
SWITCH # φψ BAD STATUS operand
SWITCH # φψ CLOSED operand
SWITCH # φψ OPEN operand
SWITCH # φψ INTERM operand, which is
disconnect pole discrepancy status
Disconnect switch φψ position control
0
Disconnect switch open commands
blocked from all sources including
protection
R/W/C
R
R
R/C
R/C
R/C
R/C
R
3
R
R/W/C
R/Ctrl
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
3-161

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents