GE B30 Communications Manual page 332

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: PhSelGAPC1
data obj. data attribute
stVal
FltCAG
stVal
Flt3Ph
stVal
FltMulti
stVal
FltVoid
stVal
3.5.2.61 Phase time overcurrent (PhsToc)
3
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60.
Table 3-107: Phase time overcurrent data objects
LNName: PhsTocPTOC#
data obj. data attribute
Str
general
dirGeneral
phsA
dirPhsA
phsB
dirPhsB
phsC
dirPhsC
Op
general
phsA
phsB
phsC
Dpo
stVal
DpoPhsβ
stVal
BlkRefγβ
setSrcRef
setSrcCB
3.5.2.62 Phase undervoltage (PhsUv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
3-94
LDevice inst: Prot
UR element: Phase select element
Type
FC UR Name
BOOLEAN
ST
PHASE SELECT BCG
SPS
BOOLEAN
ST
PHASE SELECT CAG
SPS
BOOLEAN
ST
PHASE SELECT 3P
SPS
BOOLEAN
ST
PHASE SELECT MULTI-P
SPS
BOOLEAN
ST
PHASE SELECT VOID
LDevice inst: Prot
UR element: Phase Time Overcurrent element #
Type
FC UR Name
ACD
BOOLEAN
ST
PHASE TOC# PKP
ENUMERATED
ST
BOOLEAN
ST
PHASE TOC# PKP A
ENUMERATED
ST
BOOLEAN
ST
PHASE TOC# PKP B
ENUMERATED
ST
BOOLEAN
ST
PHASE TOC# PKP C
ENUMERATED
ST
ACT
BOOLEAN
ST
PHASE TOC# OP
BOOLEAN
ST
PHASE TOC# OP A
BOOLEAN
ST
PHASE TOC# OP B
BOOLEAN
ST
PHASE TOC# OP C
SPS
BOOLEAN
ST
PHASE TOC# DPO
SPS
BOOLEAN
ST
PHASE TOC# DPO β (where β
refers to Phase-A, B or C)
ORG
ObjectReference SP
PHASE TOC# BLOCK β for group
γ (where β refers to Phase-A, B
or C)
ObjectReference SP
CHAPTER 3: IEC 61850 COMMUNICATION
Description
PHASE SELECT CAG operand
PHASE SELECT 3P operand
PHASE SELECT MULTI-P operand
PHASE SELECT VOID operand
Description
PHASE TOC# PKP operands (including
individual three phases), which indicates
Op will operate when delay expires
0, the code for unknown
0, the code for unknown
0, the code for unknown
0, the code for unknown
PHASE TOC# OP operands (including
individual three phases)
PHASE TOC# DPO operand
PHASE TOC# DPO β operands" (where β
refers to Phase-A, B or C)
PHASE TOC# BLOCK β setting for setting
group γ." (where β refers to Phase-A, B or
C)
reference to the data attribute to input
source GoCB of input if via GOOSE
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents