GE B30 Communications Manual page 421

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: DmdMtrMMTR#
data obj. data attribute
Type
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
AbMaxDm
MV
dDt
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
AcDmd
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
AcMaxDm
MV
dDt
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
WDmd
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
WMaxDmd
MV
Dt
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
VArDmd
MV
instMag
AnalogueValue
instMag.f
FLOAT32
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Meter
UR element: Signal Source # NAME Demand Metering
FC UR Name
MX
CF
CF
DmdMtrMMTR#.AbDmd.db
CF
MX
SRC # DMD IB MAX
CF
MX
SRC # DMD IC
MX
CF
CF
DmdMtrMMTR#.AcDmd.db
CF
MX
SRC # DMD IC MAX
CF
MX
SRC # DMD W
MX
CF
CF
DmdMtrMMTR#.WDmd.db
CF
MX
SRC # DMD W MAX
CF
MX
SRC # DMD VAR
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
instMag.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
SRC # DMD IB MAX, in primary amperes
with associated date, SRC # DMD IB DATE
5, the code for primary amperes
0, the code for a multiplier of 1
SRC # DMD IC, in primary amperes
instMag.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
SRC # DMD IC MAX, in primary amperes
with associated date, SRC # DMD IC DATE
5, the code for primary amperes
0, the code for a multiplier of 1
SRC # DMD W, in primary watt
instMag.f deadbanded
38 is unit for power in watts
0, the code for a multiplier of 1
power cut-off level.
SRC # DMD W, in primary watt, with
associated date, SRC # DMD W DATE
38 is unit for power in watts
0, the code for a multiplier of 1
SRC # DMD VAR, in primary volt ampere
reactive
R/W/C
R
R
R
R
R
R/W/C
R
R
R
R
R
3
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
3-183