CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-28: B90 time overcurrent data objects
LNName: B_TocPTOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
DpoPhs1
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.10 B90 undervoltage (B_Uv)
This element is instantiated in the following products: B90.
Table 3-29: B90 undervoltage data objects
LNName: B_UvPTUV#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.11 Breaker failure (BkrFa)
This element is instantiated in the following products: B30, C60, C70, D60, F60, G60, L30, L60, L90, M60, T60.
Table 3-30: Breaker failure data objects
LNName: BkrFaRBRF#
data obj. data attribute
Type
InRefγ02
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRefγ03
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRefγ04
ORG
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Time Overcurrent element #
FC UR Name
ST
TOC# PKP
ST
ST
TOC# OP
ST
TOC# DPO
ST
TOC# DPO
TOC# BLOCK for group γ
LDevice inst: Prot
UR element: B90 Undervoltage element # function
FC UR Name
ST
UNDERVOLTAGE # PKP
ST
ST
UNDERVOLTAGE # OP
ST
UNDERVOLTAGE # DPO
UNDERVOLTAGE # BLK for group
γ.
LDevice inst: Prot
UR element: Breaker Control element #
FC UR Name
3-POLE INITIATE input
BF# BLOCK.
BF# BKR POS1 φA/3P.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
TOC# PKP operand, which indicates that
Op operates when delay expires
0, the code for unknown
TOC# OP operands (including individual
three phases)
TOC# DPO operand
TOC# DPO operand
TOC# BLOCK setting for setting group γ R
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
Description
UNDERVOLTAGE # PKP operands
0, the code for unknown. It is unknown as
the element is non-directional
UNDERVOLTAGE # OP operand
UNDERVOLTAGE # DPO operand, which is
the inverse of UNDERVOLTAGE PKP
UNDERVOLTAGE # BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
BF# 3-POLE INITIATE setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BLOCK setting for setting group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS1 φA/3P setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS2 φA/3P setting for setting
group γ
R/W/C
R
R
R
R
R
R
R
R
R
3
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R