CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
Voltage Dependent Overload (Read/Write Grouped Setting)
M60
7B00
Voltage Dependent Overload Function
"
7B01
Voltage Dependent Overload Minimum
Motor Volts
"
7B02
Voltage Dependent Overload Voltage Loss 0 to 4294967295
"
7B04
VD Overload Stall Current at Minimum Volts 1.5 to 20
"
7B05
VD Overload Safe Stall Time at Minimum
Volts
"
7B06
VD Overload Acceleration Intersect at
Minimum Volts
"
7B07
VD Overload Stall Current at 100% Voltage 1.5 to 20
"
7B08
VD Overload Safe Stall Time at 100%
Voltage
"
7B09
VD Overload Acceleration Intersect at
100% Voltage
"
7B0A
Speed 2 Voltage Dependent Overload
Function
"
7B0B
Speed 2 VD Overload Minimum Motor Volts 60 to 99
"
7B0C
Speed 2 Voltage Dependent Overload
Voltage Loss
"
7B0E
Speed 2 VD Overload Stall Current at
Minimum Volts
"
7B0F
Speed 2 VD Overload Safe Stall Time at
Minimum Volts
"
7B10
Speed 2 VD Acceleration Intersect at
Minimum Volts
"
7B11
Speed 2 VD Overload Stall Current at 100%
Voltage
"
7B12
Speed 2 VD Overload Safe Stall Time at
100% Voltage
"
7B13
Speed 2 VD Acceleration Intersect at 100%
Voltage
Motor Acceleration Time (Read/Write Grouped Setting)
M60
7B20
Motor Acceleration Function
"
7B21
Motor Acceleration Current
"
7B22
Motor Acceleration Time
"
7B23
Motor Acceleration Mode
"
7B24
Motor Acceleration Block
"
7B26
Motor Acceleration Target
"
7B27
Motor Acceleration Events
"
7B28
Speed 2 Motor Acceleration Current
"
7B29
Speed 2 Motor Acceleration Time
"
7B2A
Speed 2 Motor Acceleration Mode
"
7B2B
Speed 2 Motor Acceleration Speed 1-2
"
7B2C
Speed 2 Motor Acceleration Block
"
7B2E
Reserved (9 items)
User Programmable Pushbuttons Commands (Read/Write Command) (16 Modules)
All
7B40
User Programmable Pushbutton 1 On
Command
"
7B41
...Repeated for Pushbutton 2
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
60 to 99
%
1
---
1
× FLA
0.01
0.1 to 1000
s
0.1
1.5 to 20
× FLA
0.01
× FLA
0.01
0.1 to 1000
s
0.1
1.5 to 20
× FLA
0.01
0 to 1
---
1
%
1
0 to 4294967295
---
1
× FLA
1.5 to 20
0.01
0.1 to 1000
s
0.1
1.5 to 20
× FLA
0.01
1.5 to 20
× FLA
0.01
0.1 to 1000
s
0.1
1.5 to 20
× FLA
0.01
0 to 1
---
1
1 to 10
× FLA
0.01
0.05 to 180
s
0.01
0 to 1
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
1 to 10
x FLA
0.01
0.05 to 180
s
0.01
0 to 1
---
1
0.05 to 180
s
0.01
0 to 4294967295
---
1
---
---
---
0 to 1
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F001
80
F300
0
F001
450
F001
200
F001
400
F001
600
F001
100
F001
500
F102
0 (Disabled)
F001
80
F300
0
F001
450
F001
200
F001
400
F001
600
F001
200
F001
500
F102
0 (Disabled)
F001
600
F001
1000
F097
0 (Definite
Time)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
600
F001
1000
F097
0 (Definite
Time)
F001
1000
F300
0
F001
0
F108
0 (Off)
2-117