GE B30 Communications Manual page 343

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: SubHaPHIZ1
data obj. data attribute
Type
db
INT32U
zeroDb
INT32U
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
Table 3-122: Subharmonic stator ground stage data objects
LNName: SubHa$PHIZ1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
3.5.2.73 Third harmonic neutral undervoltage (Ha3NUv)
This element is instantiated in the following products: G30, G60.
Table 3-123: Third harmonic neutral undervoltage data objects
LNName: Ha3NUvPTUV1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.74 Transformer instantaneous differential (PiDif)
This element is instantiated in the following products: T35, T60.
Table 3-124: Transformer instantaneous differential data objects
LNName: PiDifPDIF1
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
BlkRefγ
ORG
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Sub-harmonic stator ground overcurrent functions
FC UR Name
CF
SubHaPHIZ1.SHAmpAng.db
CF
SH STATOR GND BLK for group γ.reference to the data attribute to input
LDevice inst: Prot
UR element: Sub-harmonic stator ground stage $ functions
FC UR Name
ST
SH STAT GND STG$ PKP
ST
ST
SH STAT GND STG$ OP
ST
SH STAT GND STG$ DPO
LDevice inst: Prot
UR element: Third Harmonic Neutral Under Voltage element
FC UR Name
ST
3RD HARM NTRL UV PKP
ST
ST
3RD HARM NTRL UV OP
ST
3RD HARM NTRL UV DPO
3RD HARM NTRL UV BLK.
LDevice inst: Prot
UR element: Transformer Instantaneous Differential # function
FC UR Name
ST
XFMR INST DIFF OP
ST
XFMR INST DIFF OP A
ST
XFMR INST DIFF OP B
ST
XFMR INST DIFF OP C
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
0
SH STATOR GND BLK setting for setting
group γ.
source GoCB of input if via GOOSE
Description
SH STAT GND STG$ PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
SH STAT GND STG$ OP operand
SH STAT GND STG$ DPO operand
Description
3RD HARM NTRL UV PKP operands
0, the code for unknown. It is unknown as
the element is non-directional
3RD HARM NTRL UV OP operand
3RD HARM NTRL UV DPO operand, which
is the inverse of 3RD HARM NTRL UV PKP
3RD HARM NTRL UV BLK setting for
setting group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
XFMR INST DIFF OP , XFMR INST DIFF OP
A, XFMR INST DIFF OP B & XFMR INST DIFF
OP C operands
INST DIFF BLOCK setting for setting group
γ.
R/W/C
R/W/C
R
R
R/C
R/C
R/W/C
R
3
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
3-105

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents