GE B30 Communications Manual page 49

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
Subharmonic Stator Ground Actual Values (Read Only)
G60
1678
Subharmonic Injection Voltage
"
167A
Subharmonic Injection Current
"
167C
Stator Ground Resistance
"
167E
Stator Ground Resistance Exceeded
"
167F
Subharmonic Injection Current Angle
Sensitive Directional Power Actual Values (Read Only) (2 Modules)
C60, D60, F60,
1680
Sensitive Directional Power 1 Power
G30, G60, L90,
M60, N60, T60
"
1682
Sensitive Directional Power 2 Power
Restricted Ground Fault Currents (Read Only) (4 or 6 Modules)
F60, G30, G60,
16A0
Differential Ground Current Magnitude
L90, T35, T60
"
16A2
Restricted Ground Current Magnitude
"
16A4
...Repeated for Restricted Ground Fault 2
"
16A8
...Repeated for Restricted Ground Fault 3
"
16AC
...Repeated for Restricted Ground Fault 4
T35, T60
16B0
...Repeated for Restricted Ground Fault 5
"
16B4
...Repeated for Restricted Ground Fault 6
Field Unit RTD Actuals (Read Only) (8 Modules)
All except B90,
16C0
Field RTD 1 Value
L60
"
16C1
...Repeated for Field RTD 2
"
16C2
...Repeated for Field RTD 3
"
16C3
...Repeated for Field RTD 4
"
16C4
...Repeated for Field RTD 5
"
16C5
...Repeated for Field RTD 6
"
16C6
...Repeated for Field RTD 7
"
16C7
...Repeated for Field RTD 8
Field Unit Transducer Actuals (Read Only) (8 Modules)
All except B90,
16C8
Field Transducer 1 Value
L60
"
16CA
...Repeated for Field Transducer 2
"
16CC
...Repeated for Field Transducer 3
"
16CE
...Repeated for Field Transducer 4
"
16D0
...Repeated for Field Transducer 5
"
16D2
...Repeated for Field Transducer 6
"
16D4
...Repeated for Field Transducer 7
"
16D6
...Repeated for Field Transducer 8
Frequency Rate of Change Actual Values (Read Only) (2 or 4 Modules)
D30, D60, F60,
16E0
Frequency Rate of Change 1
G30, G60, L30,
L90, N60, T60
"
16E1
Reserved (3 items)
"
16E4
...Repeated for Frequency Rate of Change 2
D60, F60, G30,
16E8
...Repeated for Frequency Rate of Change 3
G60, L90, N60,
T60
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 999999.999
V
0.001 F060
0 to 999999.999
A
0.001 F060
0 to 500
kOhm
0.001 F003
0 to 0.1
---
0.1
-360 to 360
---
0.1
-2147483647 to
W
1
2147483647
-2147483647 to
W
1
2147483647
0 to 999999.999
A
0.001 F060
0 to 999999.999
A
0.001 F060
-32768 to 32767
°C
1
-32.768 to 32.767
---
0.001 F004
-327.67 to 327.67
Hz/s
0.01
0 to 65535
---
1
MEMORY MAP
Format
Default
0
0
500000
F208
(none)
F002
0
F060
0
F060
0
0
0
F002
0
0
F002
0
F001
0
2-29
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents