GE B30 Communications Manual page 411

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: ACsrcMMXU#
data obj. data attribute
Type
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
VbRMS
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
VcRMS
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
A
WYE
phsA
CMV
phsA.instCVal
Vector
phsA.instCVal.mag
FLOAT32
.f
phsA.instCVal.ang
FLOAT32
.f
phsA.cVal
Vector
phsA.cVal.mag.f
FLOAT32
phsA.cVal.ang.f
FLOAT32
phsA.units
Unit
phsA.units.SIUnit ENUMERATED
phsA.units
ENUMERATED
.multiplier
phsA.db
INT32U
phsA.dbAng
INT32U
phsA.zeroDb
INT32U
phsB
CMV
phsB.instCVal
Vector
phsB.instCVal.mag
FLOAT32
.f
phsB.instCVal.ang
FLOAT32
.f
phsB.cVal
Vector
phsB.cVal.mag.f
FLOAT32
phsB.cVal.ang.f
FLOAT32
phsB.units
Unit
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Meter
UR element: AC Source #
FC UR Name
CF
MMXU# RMS PhV.phsA
DEADBAND
CF
MX
SRC # Phase BG Voltage RMS
MX
CF
CF
MMXU# RMS PhV.phsB
DEADBAND
CF
MX
SRC # Phase CG Voltage RMS
MX
CF
CF
MMXU# RMS PhV.phsC
DEADBAND
CF
MX
SRC # Phase A Current
Magnitude
SRC # Phase A Current Angle
MX
CF
CF
MMXU# A.phsA .db
CF
MMXU# A.phsA.dbAng
CF
MX
SRC # Phase B Current
Magnitude
SRC # Phase B Current Angle
MX
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
0, the code for a multiplier of 1
voltage cut-off level.
SRC # Phase BG Voltage RMS, in primary
volts
instMag.f deadbanded
29, the code for primary volts (W/A)
0, the code for a multiplier of 1
voltage cut-off level.
SRC # Phase CG Voltage RMS, in primary
volts
instMag.f deadbanded
29, the code for primary volts (W/A)
0, the code for a multiplier of 1
voltage cut-off level.
SRC # Current phasors, in primary
amperes
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.f deadbanded
R/W/C
R
R/W/C
R
R
R
R
R
R
R
R
3
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
R
R
R
R
3-173