GE B30 Communications Manual page 136

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MEMORY MAP
Products
Address Register name
N60
78E6
"
7902
"
791E
"
793A
Validation Automation (Read/Write Setting)
All
7A00
2
Underfrequency (Read/Write Setting) (6 Modules)
D30, D60, F35,
7A60
F60, G30, G60,
L30, L90, M60,
N60, T35, T60
"
7A61
"
7A63
"
7A64
"
7A65
"
7A66
"
7A67
"
7A68
"
7A69
"
7A6A
"
7A6F
"
7A7E
"
7A8D
"
7A9C
"
7AAB
Thermal Model (Read/Write Grouped Setting)
M60
7AE0
"
7AE1
"
7AE2
"
7AE3
"
7AE4
"
7AE5
"
7AE6
"
7AE7
"
7AE8
"
7AE9
"
7AEA
"
7AEB
"
7AEC
"
7AEE
"
7AEF
"
7AF0
"
7AF1
"
7AF2
"
7AF3
"
7AF4
"
7AF5
2-116
...Repeated for PMU 3
...Repeated for PMU 4
...Repeated for PMU 5
...Repeated for PMU 6
Validation Automation Setting (16 items)
Underfrequency 1 Function
Underfrequency 1 Block
Underfrequency 1 Min Current
Underfrequency 1 Pickup
Underfrequency 1 Pickup Delay
Underfrequency 1 Reset Delay
Underfrequency 1 Source
Underfrequency 1 Events
Underfrequency 1 Target
Underfrequency 1 Reserved (5 items)
...Repeated for Underfrequency 2
...Repeated for Underfrequency 3
...Repeated for Underfrequency 4
...Repeated for Underfrequency 5
...Repeated for Underfrequency 6
Thermal Model Function
Thermal Model Curve
Thermal Model TD Multiplier
Thermal Model Bias K Factor
Thermal Model Time Constant Running
Thermal Model Time Constant Stopped
Thermal Model Hot Cold Ratio
Thermal Model RTD Bias
Thermal Model RTD Bias Minimum
Thermal Model RTD Bias Center
Thermal Model RTD Bias Maximum
Thermal Model Start Inhibit Margin
Thermal Model Block
Thermal Model Events
Thermal Model Target
Thermal Model Curve Effect
Speed 2 Thermal Model Curve
Speed 2 Thermal Model TD Multiplier
Reserved
Thermal Model IEC Curve K Factor
Thermal Model IEC Curve Time Constant
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
0 to 4294967295
---
1
0 to 1
---
1
0 to 4294967295
---
1
0.1 to 1.25
pu
0.01
20 to 65
Hz
0.01
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 5
---
1
0 to 1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 600
---
0.01
0 to 19
---
1
1 to 65000
min
1
1 to 65000
min
1
0.01 to 1
---
0.01
0 to 1
---
1
0 to 250
°C
1
0 to 250
°C
1
0 to 250
°C
1
0 to 25
%
1
0 to 4294967295
---
1
0 to 1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 5
---
1
0 to 600
---
0.01
0 to 600
---
0.01
1 to 1.5
---
0.05
0 to 1000
min.
1
UR FAMILY – COMMUNICATIONS GUIDE
Format
Default
F003
0
F102
0 (Disabled)
F300
0
F001
10
F001
5950
2000
2000
F167
0 (SRC 1)
F102
0 (Disabled)
F109
0 (Self-reset)
F001
0
F102
0 (Disabled)
F099
0 (Motor)
F001
100
F001
0
F001
15
F001
30
F001
100
F102
0 (Disabled)
F001
40
F001
130
F001
155
F001
0
F300
0
F102
0 (Disabled)
F109
0 (Self-reset)
F096
0 (Cutoff)
F099
0 (Motor)
F001
100
F001
100
F001
110
F001
45

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents