MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: SynChkRSYN#
data obj. data attribute
ctlModel
Health
stVal
Rel
stVal
RelDpo
stVal
LivV1
stVal
3
DeaV1
stVal
LivV2
stVal
DeaV2
stVal
LivDea
stVal
LivDeaDpo
stVal
LivLiv
stVal
LivLivDpo
stVal
DynOp
stVal
DynDpo
stVal
DynArmd
stVal
DifVClc
instMag
instMag.f
3-138
LDevice inst: Ctrl
UR element: Synchrocheck element # (ANSI 25)
Type
FC UR Name
CtlModels
CF
INS
ENUMERATED
ST
LPHD1.PhyHealth.stVal
SPS
BOOLEAN
ST
SYNC # CLS OP
SPS
BOOLEAN
ST
SYNC # CLS DPO
SPS
BOOLEAN
ST
SYNC # V1 ABOVE MIN
SPS
BOOLEAN
ST
SYNC # V1 BELOW MAX
SPS
BOOLEAN
ST
SYNC # V2 ABOVE MIN
SPS
BOOLEAN
ST
SYNC # V2 BELOW MAX
SPS
BOOLEAN
ST
SYNC # DEAD S OP
SPS
BOOLEAN
ST
SYNC # DEAD S DPO
SPS
BOOLEAN
ST
SYNC # SYNC OP
SPS
BOOLEAN
ST
SYNC # SYNC DPO
SPS
BOOLEAN
ST
SYNC# S-CLOSE OP
SPS
BOOLEAN
ST
SYNC# S-CLOSE DPO
SPS
BOOLEAN
ST
SYNC# S-CLOSE ARMD
MV
AnalogueValue
MX
FLOAT32
SYNCHROCHECK 1 DELTA VOLT
CHAPTER 3: IEC 61850 COMMUNICATION
Description
0 (status only)
This logical node's health
SYNC # CLS OP operand, which becomes
On all synchrocheck criteria are fulfilled.
SYNC # CLS DPO operand, which
becomes Off when all synchrocheck
criteria are fulfilled.
SYNC # V1 ABOVE MIN operand, which
indicates that V1 is above the LivVal1
setting.
SYNC # V1 BELOW MAX operand, which
indicates that V1 is below the DeaVal1
setting.
SYNC # V2 ABOVE MIN operand, which
indicates that V1 is above the LivVal2
setting.
SYNC # V2 BELOW MAX operand, which
indicates that V2 is below the DeaVal1
setting.
SYNC # DEAD S OP operand, which
indicates that live/dead conditions have
been met.
SYNC # DEAD S DPO operand, which
indicates that live/dead conditions have
not been met.
SYNC # SYNC OP operand, which
indicates that both sources are live, and
that angle, frequency and voltage
difference and range conditions have
been met.
SYNC # SYNC DPO operand, which
indicates that that one or both sources
are not live, or that angle, frequency and
voltage difference and range conditions
have been met.
SYNC# S-CLOSE OP operand, which
becomes on when all criteria for dynamic
mode are fulfilled
SYNC# S-CLOSE DPO operand, which
becomes off when all criteria for dynamic
mode are fulfilled
SYNC# S-CLOSE ARMD operand, which
becomes on when dynamic mode is
armed
SYNCHROCHECK # DELTA VOLT, in primary
volts
UR FAMILY – COMMUNICATIONS GUIDE