GE B30 Communications Manual page 344

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: PiDifPDIF1
data obj. data attribute
setSrcRef
setSrcCB
3.5.2.75 Transformer percent differential (PctDif)
This element is instantiated in the following products: G30, T35, T60.
Table 3-125: Transformer percent differential data objects
LNName: PctDifPDIF1
data obj. data attribute
Op
general
3
phsA
phsB
phsC
Blk2ndHφ
stVal
Blk5thHφ
stVal
Str
general
dirGeneral
phsA
dirPhsA
phsB
dirPhsB
phsC
dirPhsC
RefWindin
g
stVal
units
units.SIUnit
units.multiplier
DifAClc
phsθ
phsθ.instCVal
phsθ.instCVal.mag
.f
phsθ.instCVal.ang
.f
phsθ.cVal
phsθ.cVal.mag.f
phsθ.cVal.ang.f
phsθ.units
phsθ.units.SIUnit ENUMERATED
phsθ.units
.multiplier
phsθ.db
phsθ.dbAng
phsθ.zeroDb
3-106
LDevice inst: Prot
UR element: Transformer Instantaneous Differential # function
Type
FC UR Name
ObjectReference SP
INST DIFF BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Transformer Percent Differential function
Type
FC UR Name
ACT
BOOLEAN
ST
XFMR PCNT DIFF OP
BOOLEAN
ST
XFMR PCNT DIFF OP A
BOOLEAN
ST
XFMR PCNT DIFF OP B
BOOLEAN
ST
XFMR PCNT DIFF OP C
SPS
BOOLEAN
ST
XFMR PCNT DIFF 2ND θ
SPS
BOOLEAN
ST
XFMR PCNT DIFF 5TH θ
ACD
BOOLEAN
ST
logical OR of phsA, phsB & phsB
ENUMERATED
ST
BOOLEAN
ST
XFMR PCNT DIFF PKP A
ENUMERATED
ST
BOOLEAN
ST
XFMR PCNT DIFF PKP B
ENUMERATED
ST
BOOLEAN
ST
XFMR PCNT DIFF PKP C
ENUMERATED
ST
INS
INT32
ST
REFERENCE WINDING
Unit
CF
ENUMERATED
ENUMERATED
WYE
CMV
Vector
MX
FLOAT32
DIFF PHASOR Iθd magnitude, in
pu
FLOAT32
DIFF PHASOR
Vector
MX
FLOAT32
DIFF PHASOR Iθd magnitude, in
pu, with deadband
FLOAT32
DIFF PHASOR
Unit
CF
ENUMERATED
INT32U
CF
PctDifPDIF1.DifAClc.phsθ.db
INT32U
CF
PctDifPDIF1.DifAClc.phsθ.dbAng
INT32U
CF
CHAPTER 3: IEC 61850 COMMUNICATION
Description
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
XFMR PCNT DIFF OP , XFMR PCNT DIFF OP
A, XFMR PCNT DIFF OP B & XFMR PCNT
DIFF OP C operands
XFMR PCNT DIFF 2ND θ operand
XFMR PCNT DIFF 5TH θ operand
XFMR PCNT DIFF PKP A, XFMR PCNT DIFF
PKP B & XFMR PCNT DIFF PKP C operand
0
0
0
0
Number of winding used as the reference
winding for ratio compensation
1, the code for dimensionless
0, the code for a multiplier of 1
Phase differential currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
1, the code for dimensionless
-2, the code for a multiplier of Centi
4
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents