Control (Ctrl) Logical Device - GE B30 Communications Manual

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
3.5.2.83 VT fuse failure (Vtff)
This element is instantiated in the following products: C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-134: VT fuse failure data objects
LNName: VtffGAPC#
data obj. data attribute
Type
FuFail
SPS
stVal
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
Alm1
SPS
stVal
BOOLEAN
VSigLos
SPS
stV al
BOOLEAN
NeutOpn
SPS
stV al
BOOLEAN
3.5.2.84 Wattmetric ground fault (Watt)
This element is instantiated in the following products: D30, D60, F35, F60, L60, L90.
Table 3-135: Wattmetric ground fault data objects
LNName: WattPSDE#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Watt
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP

3.5.3 Control (Ctrl) logical device

The Ctrl logical device contains logical nodes that model UR control and monitoring functions.
The Ctrl logical device is available when the Advanced IEC 61850 option is purchased with the UR device.
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: VT FUSE FAILURE # function
FC UR Name
ST
SRC# VT FUSE FAIL OP
ST
SRC# VT FUSE FAIL DPO
ST
SRC# VT FF ALARM
ST
SRC# VT FUSE FAIL VOL LOSS
ST
SRC# VT NEU WIRE OPEN
LDevice inst: Prot
UR element: Wattmetric Ground Fault # settings
FC UR Name
ST
WATTMETRIC GND FLT # PKP
ST
ST
WATTMETRIC GND FLT # OP
MX
WATT GND FLT # actual value
MX
instMag.f on deadband
exception
CF
CF
WattPSDE#.Watt.db
CF
WATTMETRIC GND FLT # BLK.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
SRC# VT FUSE FAIL OP operands
SRC# VT FUSE FAIL DPO operand,
SRC# VT FF ALARM
SRC# VT FUSE FAIL VOL LOSS operand
SRC# VT NEU WIRE OPEN operand
Description
WATTMETRIC GND FLT # PKP operand
0 (unknown).
WATTMETRIC GND FLT # OP operand
SRC # Three Phase Real Power, in primary
watts
38, the code for primary watts (J/s)
0, the code for a multiplier of 1
3-phase power cut-off level in percent
multiplied by 1000
WATTMETRIC GND FLT # BLK setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R
R
R
R
R
R
3
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R/C
R/C
3-113

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents