GE B30 Communications Manual page 302

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: LinDfPDIF1
data obj. data attribute
neut.instCVal
neut.instCVal.mag
.f
neut.instCVal.ang
.f
neut.cVal
neut.cVal.mag.f
neut.cVal.ang.f
neut.units
neut.units.SIUnit ENUMERATED
neut.units
.multiplier
3
neut.db
neut.dbAng
neut.zeroDb
angRef
RstA
phsθ
phsθ.instCVal
phsθ.instCVal.mag
.f
phsθ.cVal
phsθ.cVal.mag.f
phsθ.units
phsθ.units.SIUnit ENUMERATED
phsθ.units
.multiplier
phsθ.db
phsθ.zeroDb
neut
neut.instCVal
neut.instCVal.mag
.f
neut.cVal
neut.cVal.mag.f
neut.units
neut.units.SIUnit ENUMERATED
neut.units
.multiplier
neut.db
neut.zeroDb
angRef
InRef001
setSrcRef
setSrcCB
BlkRef9
setSrcRef
setSrcCB
BlkRefγ
3-64
LDevice inst: Prot
UR element: Line Differential element (ANSI 87L) phase and general
functions
Type
FC UR Name
Vector
MX
FLOAT32
IG DIFF. CURRENT magnitude, in
primary amps
FLOAT32
IG DIFF. CU
Vector
MX
FLOAT32
IG DIFF. CURRENT magnitude, in
primary amps, with deadband
FLOAT32
IG DIFF. CU
Unit
CF
ENUMERATED
INT32U
CF
LinDfPDIF1.DifAClc.neut.db
INT32U
CF
LinDfPDIF1.DifAClc.neut.dbAng
INT32U
CF
CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
ENUMERATED
CF
WYE
CMV
Vector
MX
FLOAT32
Iθ RESTR. CURRENT magnitude,
in primary amps
Vector
MX
FLOAT32
Iθ RESTR. CURRENT magnitude,
in primary amps, with deadband
Unit
CF
ENUMERATED
INT32U
CF
LinDfPDIF1.DifAClc.phsθ.db
INT32U
CF
CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
CMV
Vector
MX
FLOAT32
IG RESTR. CURRENT magnitude,
in primary amps
Vector
MX
FLOAT32
IG RESTR. CURRENT magnitude,
in primary amps, with deadband
Unit
CF
ENUMERATED
INT32U
CF
LinDfPDIF1.DifAClc.neut.db
INT32U
CF
CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
ENUMERATED
CF
ORG
ObjectReference SP
CHNL ASYM COMP setting
ObjectReference SP
ORG
ObjectReference SP
BLOCK GPS TIME REF setting
ObjectReference SP
ORG
CHAPTER 3: IEC 61850 COMMUNICATION
Description
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
5, the code for amps
0, the code for a multiplier of 1
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
Restraint currents
5, the code for amps
0, the code for a multiplier of 1
5, the code for amps
0, the code for a multiplier of 1
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
CHNL ASYM COMP setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BLOCK GPS TIME REF setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
CURRENT DIFF BLOCK setting of setting
group γ.
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R/C
R/C
R
R/C
R/C
R

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all