CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
DynArmd
SPS
This data object indicates that dynamic mode is armed.
The SYNC1 S-CLOSE ARMD operand, which becomes On when dynamic mode is
armed.
DynDpo
SPS
The SYNC1 S-CLOSE DPO operand, which becomes Off when all criteria for
dynamic mode are fulfilled
DynOp
SPS
This data object indicates that all criteria for dynamic mode are fulfilled if value is
TRUE else false.
The SYNC1 S-CLOSE OP operand, which becomes On when all criteria for dynamic
mode are fulfilled.
Ena1
SPS
Function is Enabled.
The AR ENABLED operand.
EqLim
SPS
The number of pulses counted is equal to the set number.
Counter 1(CNT1) EQL operand, which indicates the number of pulses counted is
equal to the set number.
EqpMismat
SPS
The configuration of modules does not match the stored order code.
The EQUIPMENT MISMATCH operand.
EvtEna1
ENG
Setting to enable generation of events in event record, 0 = Disabled, 1 = Enabled
EvtLED
SPS
An LED - Event Cause LED status. For graphical front panel.
The EVENT CAUSE LED 1 operand.
EvtRcdClr
SPC
Clear Event Records (erase all Events).
The CLEAR EVENT RECORDS command.
Fail
SPS
Ground Protection Module Failure.
GPM-F (Field Ground Protection Module) Fail status.
The GPM-F FAILURE operand.
FDLOp
SPS
Overcurrent fault detector low has operated.
The 87PC FDL OP operand.
FlexErrTkn
SPS
A FlexLogic equation is incorrect.
The FLEXLOGIC ERR TOKEN operand.
Flt3Ph
SPS
Fault indication - Three phase fault.
The PHASE SELECT 3P operand.
FltAB
SPS
Fault indication - Phase A to B.
The PHASE SELECT AB operand.
FltABG
SPS
Fault indication - Phase A to B to ground.
The PHASE SELECT ABG operand.
FltAG
SPS
Fault indication - Phase A to ground.
The PHASE SELECT AG operand.
FltBC
SPS
Fault indication - Phase B to C.
The PHASE SELECT BC operand.
FltBCG
SPS
Fault indication - Phase B to C to ground.
The PHASE SELECT BCG operand.
FltBG
SPS
Fault indication - Phase B to ground.
The PHASE SELECT BG operand.
FltCA
SPS
Fault indication - Phase C to A.
The PHASE SELECT CA operand.
FltCAG
SPS
Fault indication - Phase C to A to ground.
The PHASE SELECT CAG operand.
FltCG
SPS
Fault indication - Phase C to ground.
The PHASE SELECT CG operand.
FltCntClr
SPC
TRUE = clear incipient fault count. The clear incipient fault counters command.
FltCntPhφ
INS
Number of detected incipient faults.
INCIPIENT FAULT 1 PH A/B/C FAULTS.
FltLinID
VSS
Faulted line ID
FltLocation
MV
Fault location in percentage.
The FAULT LOCATION in percentage of field winding from negative terminal in
case of single point injection. If double point injection, displays Invalid value.
FltLoopReact
MV
D30, D60, L60, L90 - The fault loop reactance
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
SynChkRSYN
SynChkRSYN
SynChkRSYN
Rec13pRREC, Rec3pRREC
DigCntFCNT
LPHD
GGIO3
LEDsIHMI
Master/LLN0
FldGnd0PHIZ
PhCmp1PDIF
LPHD
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
ICFltPTEF
ICFltPTEF
FltRFLO
FldGnd0PHIZ
FltRFLO
3-209