CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-212: FlexElement data objects
LNName: FlxElGAPC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
OpSig
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLAOT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef2
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.6.10 FlexLogic, FlexLogic timers, and virtual outputs (FlxLgc)
This element is instantiated all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60).
Table 3-213: FlexLogic data objects
LNName: FlxLgcGAPC1
data obj. data attribute
Type
Health
ENS
stVal
ENUMERATED
Indξξ
SPS
stVal
BOOLEAN
3.5.6.11 Non-volatile latches (NVLat)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-214: Non-volatile latch data objects
LNName: NVLatGAPC#
data obj. data attribute
Type
Ind1
SPS
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Gen
UR element: FlexElement element #
FC UR Name
ST
FxE # PKP
ST
ST
FxE # OP
ST
FxE # DPO
MX
FLEXELEMENT # OpSig
MX
FLEXELEMENT # OpSig on
deadband exception
CF
CF
FlxElGAPC#.OpSig.db
CF
FLEXELEMENT # BLOCK.
FLEXELEMENT # +IN
FLEXELEMENT # IN
LDevice inst: Gen
UR element: FlexLogic
FC UR Name
ST
FLEXLOGIC ERR TOKEN, 1 (Ok)
when operand is Off, 3 (Alarm)
when operand is On
ST
VOξξ On
LDevice inst: Gen
UR element: Non-Volatile Latches element #
FC UR Name
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
FxE # PKP operand, which becomes On
when this element has picked up.
0, the code for unknown
FxE # OP operand
FxE # DPO operand, which is the inverse
of FxE OP
FLEXELEMENT # OpSig, in per unit
1, the code for dimensionless (per unit)
0, the code for a multiplier of 1
0
FLEXELEMENT # BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
FLEXELEMENT # +IN setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
FLEXELEMENT # IN setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
FLEXLOGIC ERR TOKEN self-test
Virt Op ξ On (VOξξ) operand value
Description
LATCH # ON operand value
R/W/C
R
R
R
R
R
R
R
R
R
3
R
R
R
R
R
R
R/W/C
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R/W/C
R
3-195