GE B30 Communications Manual page 297

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
3.5.2.26 Generator unbalance (GnUnb)
This element is instantiated in the following products: G30, G60.
Table 3-50: Generator unbalance data objects
LNName: GnUnbPTOC1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
Table 3-51: Generator unbalance stage objects
LNName: GnUnb$PTOC1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
3.5.2.27 Ground distance (GndDis)
This element is instantiated in the following products: D30, D60, L60, L90, T60.
Table 3-52: Ground distance data objects
LNName: GndDisPDIS#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
phsA
BOOLEAN
dirPhsA
ENUMERATED
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Generator Unbalance element
FC UR Name
ST
GEN UNBAL PKP
ST
ST
GEN UNBAL OP
ST
GEN UNBAL DPO
GEN UNBAL BLK for group
LDevice inst: Prot
UR element: Generator Unbalance element Stage $
FC UR Name
ST
GEN UNBAL STG$ PKP
ST
ST
GEN UNBAL STG$ OP
ST
GEN UNBAL STG$ DPO
LDevice inst: Prot
UR element: Ground Distance Z# Settings
FC UR Name
ST
GND DIST Z# PKP
ST
ST
GND DIST Z# PKP A
ST
dirGeneral
ST
GND DIST Z# PKP B
ST
dirGeneral
ST
GND DIST Z# PKP C
ST
dirGeneral
ST
GND DIST Z# OP
ST
GND DIST Z# OP A
ST
GND DIST Z# OP B
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
GEN UNBAL PKP operands (including
individual three phases), which indicates
Op will operate when delay expires
0, the code for unknown.
GEN UNBAL OP operand
GEN UNBAL DPO operand
GEN UNBAL BLK setting for setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
GEN UNBAL STG$ PKP operand
0, the code for unknown
GEN UNBAL STG$ OP operand
GEN UNBAL STG$ DPO operand
Description
GND DIST Z# PKP operand in Phase –To –
Ground
1(Forward) if GND DIST Z DIR value is
Forward, 2 (backward) if GND DIST Z1 DIR
value is Reverse, and otherwise 0
(unknown).
GND DIST Z# OP operand
R/W/C
R
R
R
R
R
R
3
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
3-59

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents