GE B30 Communications Manual page 95

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
5DD3
...Repeated for Ground Instantaneous
Overcurrent 4
"
5DE4
...Repeated for Ground Instantaneous
Overcurrent 5
"
5DF5
...Repeated for Ground Instantaneous
Overcurrent 6
C60, C70, D30,
5E06
...Repeated for Ground Instantaneous
D60, F35, F60,
Overcurrent 7
L30, L60, L90,
M60, N60, T35,
T60
"
5E17
...Repeated for Ground Instantaneous
Overcurrent 8
"
5E28
...Repeated for Ground Instantaneous
Overcurrent 9
"
5E39
...Repeated for Ground Instantaneous
Overcurrent 10
"
5E4A
...Repeated for Ground Instantaneous
Overcurrent 11
"
5E5B
...Repeated for Ground Instantaneous
Overcurrent 12
CT Fail (Read/Write Setting) (2, 4, or 6 Modules)
D30, D60, F60,
5E6C
CT Fail 1 Function
G30, G60, L30,
L60, L90, M60,
N60, T35, T60
"
5E6D
CT Fail 1 Block
"
5E6F
CT Fail 1 Current Source 1
"
5E70
CT Fail 1 Current Pickup 1
"
5E71
CT Fail 1 Current Source 2
"
5E72
CT Fail 1 Current Pickup 2
"
5E73
CT Fail 1 Voltage Source
"
5E74
CT Fail 1 Voltage Pickup
"
5E75
CT Fail 1 Pickup Delay
"
5E76
CT Fail 1 Target
"
5E77
CT Fail 1 Events
"
5E78
...Repeated for CT Fail 2
D60, F60, G30,
5E84
...Repeated for CT Fail 3
G60, L60, L90,
M60, N60, T35,
T60
"
5E90
...Repeated for CT Fail 4
N60, T35, T60
5E9C
...Repeated for CT Fail 5
"
5EA8
...Repeated for CT Fail 6
Incipient Cable Fault Detector Actual Values (Read Only) (1, 2, or 6 Modules)
D30, F35, F60,
5EC0
Incipient Cable Fault Detector 1 Phase A
L30
Counter
"
5EC1
Incipient Cable Fault Detector 1 Phase B
Counter
"
5EC2
Incipient Cable Fault Detector 1 Phase C
Counter
F35, F60
5EC3
...Repeated for Incipient Cable Fault
Detector 2
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0 to 4294967295
---
1
0 to 5
---
1
0.1 to 2
pu
0.1
0 to 5
---
1
0.1 to 2
pu
0.1
0 to 5
---
1
0.04 to 2
pu
0.01
0 to 65.535
s
0.001 F001
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F300
0
F167
0 (SRC 1)
F001
2
F167
1 (SRC 2)
F001
2
F167
0 (SRC 1)
F001
20
1000
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F001
0
F001
0
2-75
2