GE B30 Communications Manual page 117

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
6926
Starts Per Hour Events
"
6927
Reserved (9 items)
Motor Time Between Starts (Read/Write Setting)
M60
6930
Time Between Starts Function
"
6931
Time Between Starts Minimum Time
"
6932
Time Between Starts Block
"
6934
Time Between Starts Target
"
6935
Time Between Starts Events
"
6936
Reserved (10 items)
Motor Restart Delay (Read/Write Setting)
M60
6940
Restart Delay Function
"
6941
Restart Delay Minimum Time
"
6942
Restart Delay Block
"
6944
Restart Delay Target
"
6945
Restart Delay Events
"
6946
Reserved (10 items)
Motor Mechanical Jam (Read/Write Grouped Setting)
M60
6950
Mechanical Jam Function
"
6951
Mechanical Jam Pickup
"
6952
Mechanical Jam Pickup Delay
"
6953
Mechanical Jam Reset Delay
"
6954
Mechanical Jam Block
"
6956
Mechanical Jam Target
"
6957
Mechanical Jam Events
"
6958
Reserved (8 items)
Motor Learned Data (Read/Write Setting)
M60
6960
Motor Learned Data Starts to Learn
"
6961
Motor Learned Data Calculation Period
"
6962
Reserved
Motor Learned Data Actual Values (Read Only)
M60
6963
Motor Learned Data Records Number
"
6964
Motor Learned Data Last Cleared Date
"
6966
Motor Learned Data Last Acceleration
Time
"
6967
Motor Learned Data Last Starting Current
"
6968
Motor Learned Data Last Thermal Capacity
Used
"
6969
Motor Learned Data Last Average Motor
Load
"
696A
Motor Learned Data Last Run Time After
Start
"
696C
Reserved
RTD Inputs (Read/Write Setting) (48 Modules)
All except B90
6970
RTD Input 1 Function
"
6971
RTD Input 1 ID
"
6977
RTD Input 1 Type
"
6978
RTD Input 1 Application
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
---
---
---
0 to 1
---
1
0 to 300
min
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 50000
s
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
---
---
---
0 to 1
---
1
1 to 10
x FLA
0.01
0.1 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
---
---
---
1 to 5
---
1
1 to 90
minutes 1
---
---
---
0 to 250
---
1
0 to 4294967295
---
---
0 to 655.35
s
0.01
0 to 40
× FLA
0.01
0 to 65535
%
1
0 to 40
× FLA
0.01
0 to 4294967295
hr
1
---
---
---
0 to 1
---
1
---
---
---
0 to 3
---
1
0 to 5
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F001
20
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F001
200
F001
10
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F001
1
F001
15
F001
0
F001
0
F050
0
F001
0
F001
0
F001
0
F001
0
F050
0
F001
0
F102
0 (Disabled)
F205
"RTD Ip 1"
F174
0 (100 ohm
Platinum)
F550
0 (None)
2-97
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all