GE B30 Communications Manual page 469

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
ERROR — This entry indicates that the UR encountered some type of problem when parsing, validating, or applying the
data in the CID file
INTERNAL ERROR — This entry indicates that the UR encountered an internal error. This type of entry does not normally
occur.
The text after the category describes in more detail what was encountered. ERROR entries commonly describe the process
or element that was in progress when the error occurred. Examples include "Parsing", "GOOSE subscription", "GOOSE e3-
2.0", "ReportControl", and "DAI." Additional contextual information is provided so that the location of the problem can be
found in the file.
The following is an example of a log file for a successful CID file import. Note that there are no errors reported and the CID
file loaded successfully.
2015-12-08 09:00:27.823752 : === INFORMATION: SCL file parsing started. ===
2015-12-08 09:01:09.138276 : INFORMATION: Number of ExtRef elements = 0. Number of successful GOOSE/
R-GOOSE subscriptions = 0/0.
2015-12-08 09:01:09.900773 : INFORMATION: Total number of different data in fast scan list: 0.
2015-12-08 09:01:09.900773 : INFORMATION: Total number of different data in slow scan list: 0.
2015-12-08 09:01:17.173752 : INFORMATION: File '/ram:1/ur.cid' imported.
In the following log file, the CID file load fails because the target IED IP address does not match the actual IP address of the
UR.
2015-12-08 09:20:29.890419 : === INFORMATION: SCL file parsing started. ===
2015-12-08 09:20:30.311192 : ERROR: target IED not found in file.
2015-12-08 09:20:30.311192 : ERROR: Parsing SCL file failed.
In the following log file, the CID file load fails because the lnType (logical node type) for the PhsIocPIOCx logical nodes is
missing.
2015-12-08 09:24:23.357086 : === INFORMATION: SCL file parsing started. ===
2015-12-08 09:24:42.152856 : ERROR: lnType for Logical Node 'TEMPLATEProt/PhsIocPIOC1' not found.
2015-12-08 09:24:42.152856 : ERROR: lnType for Logical Node 'TEMPLATEProt/PhsIocPIOC2' not found.
2015-12-08 09:24:42.152856 : ERROR: lnType for Logical Node 'TEMPLATEProt/PhsIocPIOC3' not found.
2015-12-08 09:24:42.152856 : ERROR: lnType for Logical Node 'TEMPLATEProt/PhsIocPIOC4' not found.
In the following log file, the CID file load fails because the IED name attribute is set to "&Test," which is not valid according
to the standard as the "&" character is not allowed here.
2015-12-08 09:34:55.007086 : === INFORMATION: SCL file parsing started. ===
2015-12-08 09:34:55.423761 : ERROR: Parsing, IED name='&Test' is invalid.
2015-12-08 09:34:55.423761 : ERROR: Parsing SCL file failed.
In the following log file, the CID file load fails because the DAI value for 'SPCSO01.sboTimeout' differs from the non-
configurable value given in the ICD file.
2015-12-08 09:47:29.540418 : === INFORMATION: SCL file parsing started. ===
2015-12-08 09:47:48.471606 : ERROR: Read only DAI 'SPCSO01$sboTimeout' (valKind="RO") in LN
'TestMaster/GGIO2' cannot be changed.
In the following log file, the CID file import is successful. Note also that the UR Private element contained some non IEC
61850 settings that have been stored in the UR but do not take effect until the UR is rebooted. Most UR settings take effect
without a reboot, and all others generate log entries as shown.
2015-12-09 03:10:55.329941 : === INFORMATION: SCL file parsing started. ===
UR FAMILY – COMMUNICATIONS GUIDE
SCL LOGGING
3
3-231

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents