GE B30 Communications Manual page 381

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: Rec3pRREC#
data obj. data attribute
Type
setSrcCB
ObjectReference SP
InRef09
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef10
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.3.26 Time between starts (TmBtwn)
This element is instantiated in the following products: M60.
Table 3-164: Time between starts data objects
LNName: TmBtwnPMRI1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
StrInh
SPS
stVal
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
StrInhTmm
INS
stVal
INT32
3.5.3.27 Transformer aging factor (Age)
This element is instantiated in the following products: G30, T35, T60.
Table 3-165: Transformer aging data objects
LNName: AgeSPTR1
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
AgeRte
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
Analogue Value MX
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Ctrl
UR element: Autoreclose element # functions
FC UR Name
AR# ADD DELAY 1 setting
AR# ADD DELAY 2 setting
LDevice inst: Ctrl
UR element: TIME BETWEEN STARTS element
FC UR Name
ST
TIME–BTWN-STARTS PKP
ST
ST
TIME-BTWN-STARTS OP
ST
TIME-BTWN-STARTS DPO
TIME-BTWN-STARTS BLK.
ST
TIME-BTWN-STARTS LO TIME
LDevice inst: Ctrl
UR element: Aging Factor Function
FC UR Name
ST
XFMR AGING FCTR OP
ST
XFMR AGING FCTR DPO
ST
XFMR AGING FCTR PKP
ST
MX
AGING FACTOR
instMag.i on deadband
exception
CF
CF
AgeSPTR1.AgeRte.db
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
source GoCB of input if via GOOSE
AR# ADD DELAY 1 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
AR# ADD DELAY 2 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
TIME–BTWN-STARTS PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
TIME-BTWN-STARTS OP operand
TIME-BTWN-STARTS DPO operand, which
is the inverse of TIME-BTWN-STARTS PKP
TIME-BTWN-STARTS BLK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
TIME-BTWN-STARTS LO TIME in min
Description
XFMR AGING FCTR OP
XFMR AGING FCTR DPO operand
XFMR AGING FCTR PKP operand
0
AGING FACTOR actual Values
1
0 is multiplier for 1
R/W/C
R/C
R
R/C
R/C
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
3-143