GE B30 Communications Manual page 293

Ur family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: DCUB_PSCH1
data obj. data attribute
Type
InRef06
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef07
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef01
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef11
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef02
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef12
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef03
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef13
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef04
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef14
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.23 Field current protection (FldAmp)
This element is instantiated in the following products: G60.
Table 3-44: Field current overcurrent data objects
LNName: FldAmpPTOC1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Directional Comparison Unblocking element
FC UR Name
GND DIR O/C FWD
GND DIR O/C REV
DCUB RX1
DCUB LOG1
DCUB RX2
DCUB LOG2
DCUB RX3
DCUB LOG3
DCUB RX4
DCUB LOG4
LDevice inst: Prot
UR element: FIELD CURRENT element over current functions
FC UR Name
ST
FIELD OC PKP
ST
ST
FIELD OC OP
ST
FIELD OC DPO
FIELD CURRENT BLK for group γ reference to the data attribute to input
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
GND DIR O/C FWD setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
GND DIR O/C REV setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB RX1 setting.
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB LOG RX1 setting (Loss of Guard)
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB RX2 setting.
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB LOG2 setting (Loss of Guard)
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB RX3 setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB LOGX3 setting (Loss of Guard)
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB RX4 setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
DCUB LOG4 setting (Loss of Guard)
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
Description
FIELD OC PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
FIELD OC OP operand
FIELD OC DPO operand
FIELD CURRENT BLK setting for setting
group γ.
source GoCB of input if via GOOSE
R/W/C
R
R/C
R
R/C
R
R/C
R
3
R/C
R
R/C
R
R/C
R
R/C
R
R/C
R
R/C
R
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
3-55

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30D60F35F60G30G60 ... Show all

Table of Contents