CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE
2.
Connect a RS-232cable to the front port relay and connect an Ethernet cable to the rear Ethernet port (crossover
cable for back-to-back connection and straight-through Ethernet cable for hub or switch) .
3.
Save all calibration settings to a file.
4.
Save all data from the relay (settings, oscillography, events).
5.
In the EnerVista 650 Setup software, select Communication > Upgrade Relay.
6.
Follow the upgrade instructions, and select the boot program bin file.
7.
Reboot the relay as required by the upgrade program.
8.
Continue with the upgrade instructions, setting the IP address and gateway when prompted.

5.1.4.2 Firmware upgrade(*)

1.
Install the proper version of the EnerVista 650 Setup software.
2.
Connect an Ethernet cable to the rear Ethernet port (a cross-over cable for back-to-back connection and straight-
through cable for hub or switch).
3.
Set the appropriate IP address in the relay.
4.
Set the appropriate IP address in the PC.
5.
In the EnerVista 650 Setup software, select Communication > Upgrade Relay.
6.
Enter the IP address, serial number, ad order code of the relay as prompted.
7.
Reboot the relay as required by the upgrade program.
8.
Locate the upgrade.txt file for the correct relay model.
9.
Click Upgrade Firmware to initiate the upgrade process.
10. Reboot the relay as required by the upgrade program to complete the upgrade process.
11. Set calibration settings (from the PC to the relay) for versions lower than 1.50.
12. All settinga and configuration are now set to the factory default.
13. Send new settings and configuration files to the relay if needed.
(*) The boot code upgrade must be performed using a crossed copper cable (RJ45) connected to the PC. It is not necessary
to modify the internal fiber/cable switch, as the upgrade is carried out at 10 Mb/s, and thus there is no cable/fiber
conflict.This does not apply to the firmware upgrade, which can be performed either with the Ethernet fiber connection, or
with the cable connection.
Note: See chapter 13 F650 TROUBLESHOOTING GUIDE if there is any problem during the upgrade process.
GEK-113000-AF