CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES

3.1.6.7 Setting checksum calculation

When working in offline mode, the Settings Checksum calculation option calculates the CRC of different configured
settings for the open *.650 file. When a *.650 file is uploaded to the relay, the calculated Settings Checksum and the actual
value of the Settings Checksum read from the relay (Actual values > Status > System Info) must match.
In order to calculate this checksum, the following sections of the * .650 file are considered:
All settings in the relay configuration section (Setpoint > Relay configuration) excluding:
Those communication settings: Setpoint > Product Setup > Communication settings > SerialPorts or
Network (Ethernet) or Modbus Protocol or Routing
Relay calibration factors
Opening and closing time in the Switchgear section

3.1.7 Setpoint menu

Setpoint
Product Setup
System Setup
Protection Elements
Control Elements
Inputs/Outputs
Quick Settings
Relay Configuration
Logic Configuration
Procome
Configuration
IEC103 Configuration
Clock (*)
(*) indicates online only, (**) indicates offline only
GEK-113000-AF
Communications settings for all protocols and physical mediums. ModBus user map
definition, fault report, oscillography, data logger demand settings and Time Settings.
General Settings, Flex Curves Definition, Breaker settings, maintenance, switchgear
snapshot events management and Miscellaneous Settings.
Phase, Neutral, Ground, Sensitive Ground and Negative Sequence Current Settings.
Voltage Elements settings and Power Settings management.
Setting groups, under- and over-frequency settings, synchrocheck, autoreclose, breaker
failure, VT fuse failure, broken conductor, locked rotor settings management, Pulse
Counters, Analog comparators, Frequency Rate of Change, Load encroachment, max
number of starts, Digital Counters, Cold Load Pickup and PLC Timer Masks
Contact I/O settings for all boards available in device, Remote Comms Force Outputs and
Virtual inputs.
Menu that encompass the most important settings to configure the device such as;
Current and Voltage sensing or current protection element.
Configuration of Outputs, LEDs, Operations, Protection Elements, Oscillography, Control
Events, Control Elements, Switchgear, Inputs, Virtual Inputs, Operations and HMI. Whole
relay configuration with internal relay signals or user-definable ones as logic (virtual
outputs).
Logic configuration graphic editor (PLC Editor). It is a PLC Project file editor that contains all
the internal drawings used to make the logic (virtual outputs) based on IEC 61131-3
standard. Functional block diagram (FDB).
Procome Configuration tool. Only available for Procome models (5) when communicating
through Ethernet with EnerVista 650 Setup
IEC103 settings for available IEC103 models (3) when communicating through Ethernet
with Enervista 650 Setup
Relay synchronization to computer clock or to user-definable date and time. Online mode
only.
F650 DIGITAL BAY CONTROLLER
3.1 ENERVISTA 650 SETUP SOFTWARE
3-17