5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00.
18. Click Yes to start the process, beginning with the relay flash memory deletion.
At this point all the information stored in the relay is lost. Until now, no important change has been made to the relay,
the boot memory upgrading process has just been prepared.
This process can take several minutes, during which a progress bar is displayed.
19. If the process is successful, continue to step 20.
If the process is unsuccessful and the relay gets stuck at "Sending file imagen_kernel..." (see figure below)
This error may be due to no communication via the Ethernet port. At this point serial communications work properly,
the relay flash memory has been erased, and the upgrade procedure must be completed to start working with the
unit. If the procedure is not completed, the HMI shows the message "OS Loading..." and the relay does not start up.
In this case refer to step 4 above
If all points from step 4 are correct but the problem persists:
Disable and Enable the Ethernet connection while the files are being sent (during the "Sending file..." message -
previous figure). To do this, in Windows OS go to Startup > Control Panel > Network Connection > Local Network,
right-click and select Disable. Now the Local Network status Icon is shown as Disabled. In the same screen right-click
Local Network, select Enable, and wait until Enabled status is shown.
20. Once the memory has been erased and the files upgraded in the relay, the parameters for the Ethernet
communications must be set. The requested values are the IP address and the gateway.
5-10
F650 DIGITAL BAY CONTROLLER
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE
GEK-113000-AF