D.1 FACTORY DEFAULT SETTINGS
Lowset pickup level
Internal arc pickup level
Internal arc time delay
Retrip time delay
Hiset time delay
Lowset time delay
Second stage time delay
WITHOUT current element time delay
Snapshot event generation
Setpoint > Control Elements > VT Fuse Failure)
Setting Description
Function permission
Snapshot event generation
Setpoint > Control Elements > BROKEN CONDUCTOR
Broken Conductor 1 > Broken Conductor 2 > Broken Conductor 3
Setting Description
Function permission
Tap Level in percentage of I2/I1
Trip Time
Snapshot event generation
Current Inhibition Level setting
Setpoint > Control Elements > Locked Rotor
Locked Rotor 1 > Locked Rotor 2 > Locked Rotor 3
Setting Description
Function permission
Input type
Full load current
Pickup level
Trip time
Reset time
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION
Pulse counter enabling setting
Name of the pulse counter
D-22
Lowset Pickup
2.00
Internal Arc Pickup
0.10
Internal Arc Delay
10.00
Supervision Delay
10.00
HiSet Delay
10.00
LowSet Delay
10.00
2nd Step Delay
10.00
No Current Delay
10.00
Snapshot Events
ENABLED
Name
Default Value
Function
DISABLED
Snapshot Events
ENABLED
Name
Default Value
Function
DISABLED
Tap
20
Trip Delay
60
Snapshot Events
ENABLED
Operation Threshold
0.005
Name
Default Value
Function
DISABLED
Input
PHASOR(DFT)
Full Load Current
0.50
Pickup Level
1.01
Trip Delay
0.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
CntPulses Enabled X
DISABLED
CntPulses Name X
Pulse Counter 1
F650 DIGITAL BAY CONTROLLER
0.01
[0.05 : 160.00]
A
0.01
[0.05 : 160.00]
A
0.01
[0.00 : 900.00]
s
0.01
[0.00 : 900.00]
s
0.01
[0.00 : 900.00]
s
0.01
[0.00 : 900.00]
s
0.01
[0.00 : 900.00]
s
0.01
[0.00 : 900.00]
s
N/A
[DISABLED – ENABLED]
Step Range
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
Step Range
N/A
[DISABLED – ENABLED]
0.10
[20.0 : 100.0]
%
0.01
[0.00 : 900.00]
s
N/A
[DISABLED – ENABLED]
0.00
[0.000 : 1.000]
1 A
Step Range
N/A
[DISABLED – ENABLED]
N/A [PHASOR – RMS]
KA
[0.10 : 10.00]
N/A [1.01 : 109.00]
s
[0.00 : 900.00]
s
[0.00 : 900.00]
N/A [DISABLED – ENABLED]
STEP RANGE
N/A
[DISABLED – ENABLED]
N/A
N/A
APPENDIX D:
User
Value
User
Value
User
Value
USER
VALUE
GEK-113000-AF