GE F650 User Manual page 268

Grid solutions digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

D.1 FACTORY DEFAULT SETTINGS
Values for reset points 0.05 pkp
...
Values for reset points 0.97 pkp
Values for reset points 0.98 pkp
Values for operation points 1.03 pkp
Values for operation points 1.05 pkp
...
Values for operation points 19.50 pkp
Values for operation points 20.00 pkp
Setpoint > System Setup > Breaker > Breaker Settings
Setting Description
Number of Switchgear selected as breaker Number of Switchgear 1
Maximum value of KI2t
KI2t integration time
Maximum number of openings
Maximum Openings in one hour
Snapshot Event generation
Setpoint > System Setup > Breaker > Breaker Maintenance
Setting Description
KI2t Counter Phase A
KI2t Counter Phase B
KI2t Counter Phase C
Openings counter
Closings counter
Setpoint > System Setup > Switchgear
Setting Description
Snapshot Event generation for switchgear
#1
Snapshot Event generation for switchgear
#2
Snapshot Event generation for switchgear
#3
Snapshot Event generation for switchgear
#4
D-12
Time 0.05xPKP [RST]
0.000
...
...
Time 0.97xPKP [RST]
0.000
Time 0.98xPKP [RST]
0.000
Time 1.03xPKP [OP]
0.000
Time 1.05xPKP [OP]
0.000
...
...
Time 19.50xPKP [OP]
0.000
Time 20.00xPKP [OP]
0.000
Name
Default Value
Maximum KI2t
9999.99
KI2t Integ. Time
0.03
Maximum Openings
9999
Max.Openings 1 hour
40
Snapshot Events
ENABLED
Name
Default Value
KI2t BKR Ph A Cnt
0.00
KI2t BKR Ph B Cnt
0.00
KI2t BKR Ph C Cnt
0.00
BKR Openings Cnt
0
BKR Closings Cnt
0
Name
Default Value
Snapshot Events
DISABLED
SWGR 1
Snapshot Events
DISABLED
SWGR 2
Snapshot Events
DISABLED
SWGR 3
Snapshot Events
DISABLED
SWGR 4
F650 DIGITAL BAY CONTROLLER
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
0.00
[0.000 : 65.535]
1 s
Step Range
1
[1 : 16]
0.01(
KA)2
[0.00 : 9999.99]
s
0.01s [0.03 : 0.25]
1
[0 : 9999]
1
[1 : 60]
N/A
[DISABLED – ENABLED]
Step Range
0.01
(KA)2
[0.00 : 9999.99]
s
0.01
(KA)2
[0.00 : 9999.99]
s
0.01
(KA)2
[0.00 : 9999.99]
s
1
[0 : 9999]
1
[0 : 9999]
Step Range
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
APPENDIX D:
User
Value
User
Value
User
Value
GEK-113000-AF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents