CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES
Table 3-1: Types of files generated by EnerVista 650 Setup software, offline:
Settings & Configuration File *.650
Description
Settings and Configuration Section
Created by
EnerVista 650 Setup
Contents
Relay configuration file containing all elements
Settings, input/output and LEDs configuration, graphic
display configuration, etc.
Equations corresponding to the logic created and
compiled in the PLC Editor
How to save
EnerVista 650 Setup:
File > Save *
How to open
EnerVista 650 Setup:
File>Open *
How to
Connect with the relay (Communications > Computer)
transfer to
Open the created file (File > Open *)
relay
Send to relay from the menu: File > Send info to relay
Note that texts used in the configuration of inputs,
outputs, etc. are not sent to the relay. The only texts
sent to relay are operations, events, and LEDs.
When using element libraries (both pre-existing in File Library > Open Library or created by the user in File Library > New
Library), the program creates and manages the corresponding files (*.lib) in a folder named FDB (Functional Block
Diagram). These files are used for PLC project compilation. The element library files must be stored with the other logic
configuration files that build the PLC project (*.pep, *.aut, *.lib).
Besides sending configuration information to the relay (Settings & configuration in *.650 format), storing the complete set
of *.650, *.pep, *.aut and *.lib files inside the relay is recommended (Communication > Upload info files to relay). This
ensures that logic configuration files are available in future for logic modifications. Even if these files are not used by the
relay, they are required to connect to the relay and analyze its configuration. The EnerVista 650 Setup software program
manages the logic configuration files globally, so that when the *.pep file is uploaded to the relay, the associated *.aut and
*.lib files are also stored.
File storage inside the relay
(RECOMMENDED)
Retrieval of files stored in the relay
(RECOMMENDED)
GEK-113000-AF
Logic Configuration Files (*.pep, *aut, *.lib)
*.pep
Header for Logic
project
Logic configuration
graphic editor (PLC
Editor)
PLC project file
containing the
necessary
information
relative to the relay
model, logic
libraries included in
the project (*.lib),
graphic file name
(*.aut), etc.
PLC Editor:
File > Save Project
PLC Editor:
File > Open Project
Connect with the relay (Communications > Computer)
Launch Logic equations Editor (Setpoint > Logic
Configuration)
Open the created PLC project (File > Open Project)
Compile the project (Run > Compile)
Now the logic (virtual outputs) can be sent directly to relay
(Run > Send Equations to Relay). Texts of virtual outputs are
not stored in the relay, only in the logic configuration files to
be edited.
Communication > Upload info files to relay through Ethernet
Communication > Download info files from relay through Ethernet
F650 DIGITAL BAY CONTROLLER
3.1 ENERVISTA 650 SETUP SOFTWARE
*.aut
*.lib
Graphical edition
User programmable
container. Logic
logic objects
equations (Virtual
Outputs) in FDB
format.
Logic configuration
Logic configuration
graphic editor (PLC
graphic editor (PLC
Editor)
Editor)
PLC Project file
Library file to be
containing all the
included as an
drawings used by
object in a PLC
the logic, required
project. Logic
by 650 relay based
packages that can
on IEC 61131-3
be stored into
standard. Functional
libraries and be
block diagram (FDB).
distributed in
different PLC
projects.
PLC Editor:
PLC Editor:
File > Save Project
File > Save Library
PLC Editor:
PLC Editor:
File > Open Project
File > Library > New
Library
3-7