6.2 OUT OF SERVICE SETTING

CHAPTER 6: COMMISSIONING
6.2 Out of service setting
The Relay Out Of Service setting is configured in Setpoint > System Setup > Miscellaneous. The unit also has an Out of
Service status that is configured in Relay configuration > Protection elements. When active, these states stop all
changes to PLC equations and functions, including changes to the input/output boards, so if there is a change in any input
or output the unit will not show this change until it has returned to ready mode. For example if an output is closed and the
unit goes to the Out of Service state, the output is kept closed even if the state that closed it changes and would otherwise
open the output. When the unit goes out of the Out of Service state, the output is then opened.
When the Out of Service status goes to ON, or the setting has been changed to Enabled, the ready LED also changes to
red. Be careful if ready LED is linked to an output, because the output will not change its state. To set outputs to ready
state see factory default Logic & Configuration in the detailed manual. Take notice that, in the default configuration, the
general setting out of service is enabled, so it is necessary to change to disabled to start working with the unit
The following figure shows the flow chart of these states