3.2 HUMAN-MACHINE INTERFACE (HMI)
In the second option, fault reports can be viewed through the HMI Fault Report menu accessed by pressing the enter/
shuttle key. The display shows information from the last ten faults, including both general information and metering
screens for each fault. Displayed information starts with the most recent fault, and previous faults can be viewed by
rotating the enter/shuttle key.
Displayed information is stored in the relay volatile memory, so if the relay is turned off this information is lost, as also
happens if a Clear Fault Report command is executed. However, saved fault reports stored in the relay non-volatile
memory remain after the Fault reset, and can be obtained from the relay using the EnerVista 650 Setup software, Actual >
Records > Fault report.
If there is no fault report available through the display, the relay shows a Fault report not available message.
The format of the displayed screens is as follows:
Possible fault types are as follows:
GROUND
PHASE
3-46
Select the Fault report menu in text menu
If there is more than one fault record press the up-down keys or rotate the shuttle
key and select the desired record to be displayed.
First screen with general fault information: Fault report #number, fault type,
distance and date and time.
Second screen with metering data for that fault record. All this data is a summary
from the fault report file that can be retrieved via EnerVista 650 Setup software.
Figure 3-25: Fault report navigation in HMI
Ground faults
AG
phase A to ground
ABG phase AB to ground
BG
phase BG to ground
BCG phase BCG to ground
CG phase CG to ground
CAG phase CAG to ground
Phase to phase faults
F650 DIGITAL BAY CONTROLLER
CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES
GEK-113000-AF