CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE
Note: To assure that the configuration is correctly setup it is possible to perform a ping command from the PC.
Then the PC settings should be the same pattern as follows:
IP Address:192.168.37.xxx
Netmask:255.255.255.0
Gateway:192.168.37.10 (if desired)
Where XXX is a number between 0 and 255 that is not assigned to any other device to avoid collisions.

5.2.2 Firmware version upgrade

5.2.2.1 Introduction

1.
The relay settings and configuration will be lost, so it is advisable to save them to a file.
2.
In case of error during the firmware upgrading process, the user can repeat the whole process as many times as
necessary.
3.
Firmware upgrading process should be done using the EnerVista 650 Setup software and Ethernet connection (Port
ETH_E, A or B) via Cross-Over RJ45 Ethernet cable.

5.2.2.2 Firmware upgrade

1.
Once the communication with the relay through Ethernet connection has been verified, enter the EnerVista 650 Setup
program, select Communication and the Upgrade Relay option on the top menu bar.
2.
Select Device Upgrade FW&Boot>=7.00 and click [...] to browse for the file. The appropriate *.SFD file should be
obtained from,
http://www.gegridsolutions.com/index.htm
facility. The file must be saved in the root drive or in the desktop of the PC. Choose the corresponding firmware file for
upgrading the device.
GEK-113000-AF
or from The Technical Service Dept. at any GE Multilin
F650 DIGITAL BAY CONTROLLER

5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE

5-23