Inputs/Outputs Menu; Records Menu - GE F650 User Manual

Grid solutions digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

CHAPTER 3: INTERFACES, SETTINGS & ACTUAL VALUES

3.1.8.4 Inputs/Outputs menu

The Inputs/Outputs menu includes all the inputs and outputs signals available in the device. Contact and virtual type.
inputs/outputs
Contact Inputs
Contact Output Status
Contact Outputs
Operates
Contact Outputs
Resets
IO Board Status
Virtual Inputs
Virtual Outputs
Remote Outputs
Remote Inputs
Analog Inputs (*)
Virtual Output Latched
Virtual output
Analogue
(*) indicates online only, (**) indicates offline only

3.1.8.5 Records menu

The Records menu is only available in online mode and includes the possibility to retrieve all the records available in the
device. By serial or Ethernet.
Records (*)
Event recorder (*)
Waveform capture (*)
Fault Report (*)
Data logger (*)
(*) indicates online only, (**) indicates offline only
GEK-113000-AF
Status of digital inputs in the Relay for each board according to the relay model.
Status of digital outputs in the Relay for each board according to the relay model.
Status (activated or not) of the variables used to operate a contact output. To configure
these signals go to Setpoint > Relay Configuration > Outputs menu.
Status (activated or not) of the variables used to reset a contact output. To configure these
signals go to Setpoint > Relay Configuration > Outputs menu. This output reset
Command is only effective if latch is selected for Output Type setting on the I/O board,
thus the contact output has been configured to emulate function 86 (latching relay).
Status of I/O boards. This status provides if the hardware it is OK (boards matching relay
model, correctly inserted in their tracks, in good state and communicating through the
internal CAN bus).
Status of Virtual inputs latched (32) and self-reset (32).
Status of virtual outputs (configured in PLC Editor). Up to 512.
States of remote outputs for IEC61850 models.
Status of remote device and remote inputs for IEC61850 models.
Measurements coming from analog inputs (DCMA)
Status of Virtual Output Latched (configured in PLC Editor). Up to 16.
Status of Virtual OutputAnalogues configured in PLC Editor). Up to 49 float values and 49
integer values can be used.
Retrieval and visualization of snapshot event (all and new), control events and alarm panel.
By serial or Ethernet (ModBus RTU or TCP/IP)
Retrieval of oscillography files, by Ethernet.
Retrieval and visualization of fault report files, by Ethernet.
Retrieval and visualization of data logger files. Only by Ethernet.
F650 DIGITAL BAY CONTROLLER
3.1 ENERVISTA 650 SETUP SOFTWARE
3-31